ELE07-01876
| Electrical Rough-In | 5/25/2007 | 5/25/2007 | 5/25/2007 3:41:06 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ric ok ,talked to contr about can lights in new wine closet, said that new construction not supposed to be remodel type, need to ensure that insulation not in contact with cans that get installed, Tom is elect.
|
ELE07-01876
| Final | 5/25/2007 | 5/25/2007 | 5/25/2007 3:28:39 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer wrong type inspection request, see ri
|
ELE07-00316
| Final | 5/25/2007 | 5/25/2007 | 5/25/2007 2:54:36 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 5/25/2007 at 8:17:03 AM. Contact: ###-####. ok to final, signed occ card
|
ELE07-00913
| Final | 5/25/2007 | 5/25/2007 | 5/25/2007 2:27:39 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 5/25/2007 at 8:16:25 AM. Contact: ###-####. ok to final, signed occ card
|
ELE06-02052
| Final | 5/25/2007 | 5/25/2007 | 5/25/2007 2:02:20 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 5/25/2007 at 8:15:31 AM. Contact: ###-####. ok to final, no card to sign
|
ELE07-00704
| Final | 5/25/2007 | 5/25/2007 | 5/25/2007 1:23:17 PM | P | FAIL |
|
|
craig; Phone #: ###-#### - please call for access Internet Inspection Request from: Victoria Beall called, left corr notice, nec 422.16(B)(2) disposal cord shall not be over 3', 408.4 circuit directory shall be clear, concise and direct for each ckt, 210.12(B) bedrooms shall have afci protection, 422.31(B) shall provide lockout or disconnect for hw heater, 410.8(D) shall have minimum 12" from edge of shelf to edge of fixture in closet, 406.4(D) faceplates shall allow recpts to be flush with or project from faceplate, 410(D) luminaire within 3' of shower shall be listed for wet location if subject to shower spray, BCC kitchen gfci shall operate, 3-way switch to basement shall be wired correctly, nec 110.26 shall provide clearances at garage panel, 250 shall provide grounding for garage
|
ELE07-01899
| Final | 5/25/2007 | 5/25/2007 | 5/25/2007 12:24:35 PM | P | PASS |
|
|
pat; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final
|
ELE07-01873
| Conference | 5/24/2007 | 5/25/2007 | 5/25/2007 11:49:48 AM | A | DONE |
|
|
tom ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith talked about bringing addition up to code
|
ELE07-01894
| Electrical Rough-In | 5/25/2007 | 5/25/2007 | 5/25/2007 10:35:38 AM | A | FAIL |
|
|
###-#### Internet Inspection Request from: Todd Holbrook called, left message, left corr notice, nec 210.52(A)(2) there shall be recpt on 2' wall space(ne up br), 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 334.30 nm cable shall be stapled within 12" of panel, need to look at service when called in, check for sub-panel gnd and neut isol, range and dryer 4-wire
|
ELE07-01827
| Electrical Rough-In | 5/24/2007 | 5/25/2007 | 5/25/2007 9:50:57 AM | A | PASS |
|
|
rick - special instructions the bld is at 1115 e jefferson ; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, ric ok
|
ELE07-01811
| Final | 5/24/2007 | 5/25/2007 | 5/25/2007 9:08:30 AM | A | PASS |
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, ok to final
|
ELE07-01088
| Electrical Rough-In | 5/24/2007 | 5/25/2007 | 5/25/2007 8:42:23 AM | A | PASS |
|
|
mike Note: underground; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles west side u/g ok to cover
|
ELE07-01217
| Final | 5/24/2007 | 5/25/2007 | 5/25/2007 8:11:56 AM | A | PASS |
|
|
bruce; Phone #: ###-#### Internet Inspection Request from: Victoria Beall had elect do a couple of small fixes, ok to final, signed occ card
|
ELE06-03238
| Final | 5/24/2007 | 5/25/2007 | 5/24/2007 12:52:57 PM | A | CANC |
|
|
David ; Phone #: ###-#### Internet Inspection Request from: Victoria Beall Disp set to [CANC] by a contractor via Hello! on May 24 2007 12:52PM.
|