BLD07-00279
| FIRE-Final Inspection | 5/25/2007 | 5/25/2007 | 5/25/2007 2:54:21 PM | P | FAIL |
|
|
Provide signage and visual lock indicator at the main entry/exit door, provide approved hardware at the second storefront door.
|
MIS07-00048
| FIR-Final | 5/24/2007 | 5/25/2007 | 5/25/2007 2:49:57 PM | P | NH |
|
|
No access at the time of inspection.
|
BLD07-00568
| FIRE-Final Inspection | 5/24/2007 | 5/25/2007 | 5/25/2007 2:48:54 PM | A | PASS |
|
|
Life safety inspection passed.
|
FIR06-00664
| INSP-Supply line flush | 5/24/2007 | 5/25/2007 | 5/25/2007 1:49:03 PM | P | NR |
|
|
Work not yet complete for inspection.
|
FIR07-00103
| INSP-Sprinkler Rough-in | 5/24/2007 | 5/25/2007 | 5/25/2007 1:48:22 PM | P | NR |
|
|
Work not yet completed for inspection.
|
BLD07-00360
| FIRE-Final Inspection | 5/24/2007 | 5/25/2007 | 5/25/2007 1:30:00 PM | P | CANC |
|
|
###-####
|
FIR06-00966
| FIR-Aging Inspection | 5/25/2007 | 5/25/2007 | 5/25/2007 1:16:04 PM | | DONE |
|
|
wip
|
FIR07-00368
| INSP-Sprinkler Rough-in | 5/24/2007 | 5/25/2007 | 5/25/2007 1:15:02 PM | A | FAIL |
|
|
Heads in sales office 106 are overspaced.
|
FIR05-00822
| INSP-Final Inspection | 5/24/2007 | 5/25/2007 | 5/25/2007 1:05:59 PM | A | DEFR |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|
BLD06-03595
| FIRE-Final Inspection | 5/25/2007 | 5/25/2007 | 5/25/2007 12:47:51 PM | P | DEFR |
|
|
Inspection to be rescheduled.
|
FIR06-01017
| INSP-Alarm Testing | 5/24/2007 | 5/25/2007 | 5/25/2007 12:30:41 PM | P | CANC |
|
|
No time available to complete inspection today, to be rescheduled per conversation with contractor.
|
FIR07-00394
| INSP-Sprinkler Rough-in | 5/23/2007 | 5/25/2007 | 5/25/2007 12:29:14 PM | P | FAIL |
|
|
One head in the storage room is blocked by an adjacent surface mounted light fixture, one pendent at the reception area is overspaced off the wall.
|
FIR06-00645
| INSP-Final Inspection | 5/23/2007 | 5/25/2007 | 5/25/2007 11:11:12 AM | A | PART |
|
|
Verified required corrections, a/v notification tested acceptable, all dampers functioned properly except #77 which will need repair and retest, manual pulls and door release are satisfactory, smoke and heat detectors not tested at this time due to time constraints, will test remainder of alarm work at next scheduled inspection as discussed.
|