Inspections for the day of: Wednesday, May 25, 2016.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00099 ELE-Aging Inspection5/25/20165/25/20165/27/2016 3:35:04 PM PASS
Owner refuses to comply. Future fees will apply.
ELE16-00329 Electrical Rough-In5/25/20165/25/20165/25/2016 3:48:48 PMPFAIL
Ceiling
Late pm if possible please Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Addressed existing conduits and boxes, All conduits supported by wires shall be secured at top and bottom. Too many open boxes in perimeter rooms. Will check on existing low voltage cable in plenum rated ceiling. Bond required on cable tray
ELE16-00521 Final5/24/20165/25/20165/25/2016 1:55:41 PMPPASS
Chris is the contact his cell no is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
Final ok
ELE16-01666 Electrical Rough-In5/25/20165/25/20165/25/2016 1:54:14 PMPPASS
walls only Phone #: ###-#### Inspection requested via web by Dan Rohl
Wall rough in ok cover
ELE16-00303 Electrical Rough-In5/25/20165/25/20165/25/2016 12:21:18 PMPPASS
3rd floor wall rough in for cover BSU T.I. Contact is Eric Gibson ###-####. Phone #: ###-#### Inspection requested via web by Toby Groves
Perimeter walls accept wall to stair platform not present. Rough in ok cover
ELE15-00495 Electrical Rough-In5/25/20165/25/20165/25/2016 11:57:24 AMAPASS
2nd floor electric room of 5 story. Wall rough in for cover. Contact is Eric Gibson. ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves
Walls rough in ok cover and noted in book
ELE13-01291 Electrical Rough-In5/24/20165/25/20165/25/2016 10:48:43 AMAPASS
underground site work inspection near 9th St. Call Frank at number above. Phone #: ###-#### Inspection requested via web by Brandon Robinson
Underground N. E. of drains in vent lawn area rough in ok cover
ELE15-01617 Electrical Rough-In5/24/20165/25/20165/25/2016 10:08:23 AMAPASS
Underground
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Parking lot underground 2 east trenches and 4 interior pole bases rough in ok cover. Discussed travel areas in parking area ok to cover trenches prior to inspection if photos are taken.
ELE15-03377 Final5/24/20165/25/20165/25/2016 9:27:58 AMAFAIL
Contact will be Tom. Thank you! Phone #: ###-#### Inspection requested via web by Stacie t
110.3(B)- Exhaust fan located in shower stall shall have GFCI protection as per manufacturers instructions.
210.8(A)(1)- All 120 volt receptacle outlets located in bathroom area shall have GFCI protection. washer. GFCI device shall be located in a readily accessible location.
210.12- All 120 volt outlets located in bedroom areas shall have AFCI protection. Smokes and closet switch.
406.12- All receptacle outlets 15 or 20 amp 120 volt shall be tamper resistant type if installed in or on a dwelling unit.
Called contact, no answer, voicemail not set up yet. Left correction notice.
ELE16-01628 Conference5/24/20165/25/20165/25/2016 8:38:03 AMADONE
8 am if possible please to coordinate with other trades
Ryan Barnes
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Discussed dedicated electrical space for panel boards. Job has been designed with duct work over panel boards limiting dedicated space. As per NEC 110.26(E) area shall be clear width and depth of equipment from floor to 6' above or to structural ceiling. Contractor to explore other locations for panels.
Also asked to change egress dor of electrical room to open out and have panic hardware installed.