ELE11-00099
| ELE-Aging Inspection | 5/25/2016 | 5/25/2016 | 5/27/2016 3:35:04 PM | | PASS |
|
|
Owner refuses to comply. Future fees will apply.
|
ELE16-00329
| Electrical Rough-In | 5/25/2016 | 5/25/2016 | 5/25/2016 3:48:48 PM | P | FAIL |
|
|
Ceiling Late pm if possible please Phone #: ###-#### Inspection requested via web by Kerri Hamilton Addressed existing conduits and boxes, All conduits supported by wires shall be secured at top and bottom. Too many open boxes in perimeter rooms. Will check on existing low voltage cable in plenum rated ceiling. Bond required on cable tray
|
ELE16-00521
| Final | 5/24/2016 | 5/25/2016 | 5/25/2016 1:55:41 PM | P | PASS |
|
|
Chris is the contact his cell no is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates Final ok
|
ELE16-01666
| Electrical Rough-In | 5/25/2016 | 5/25/2016 | 5/25/2016 1:54:14 PM | P | PASS |
|
|
walls only Phone #: ###-#### Inspection requested via web by Dan Rohl Wall rough in ok cover
|
ELE16-00303
| Electrical Rough-In | 5/25/2016 | 5/25/2016 | 5/25/2016 12:21:18 PM | P | PASS |
|
|
3rd floor wall rough in for cover BSU T.I. Contact is Eric Gibson ###-####. Phone #: ###-#### Inspection requested via web by Toby Groves Perimeter walls accept wall to stair platform not present. Rough in ok cover
|
ELE15-00495
| Electrical Rough-In | 5/25/2016 | 5/25/2016 | 5/25/2016 11:57:24 AM | A | PASS |
|
|
2nd floor electric room of 5 story. Wall rough in for cover. Contact is Eric Gibson. ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves Walls rough in ok cover and noted in book
|
ELE13-01291
| Electrical Rough-In | 5/24/2016 | 5/25/2016 | 5/25/2016 10:48:43 AM | A | PASS |
|
|
underground site work inspection near 9th St. Call Frank at number above. Phone #: ###-#### Inspection requested via web by Brandon Robinson Underground N. E. of drains in vent lawn area rough in ok cover
|
ELE15-01617
| Electrical Rough-In | 5/24/2016 | 5/25/2016 | 5/25/2016 10:08:23 AM | A | PASS |
|
|
Underground Phone #: ###-#### Inspection requested via web by Kerri Hamilton Parking lot underground 2 east trenches and 4 interior pole bases rough in ok cover. Discussed travel areas in parking area ok to cover trenches prior to inspection if photos are taken.
|
ELE15-03377
| Final | 5/24/2016 | 5/25/2016 | 5/25/2016 9:27:58 AM | A | FAIL |
|
|
Contact will be Tom. Thank you! Phone #: ###-#### Inspection requested via web by Stacie t 110.3(B)- Exhaust fan located in shower stall shall have GFCI protection as per manufacturers instructions. 210.8(A)(1)- All 120 volt receptacle outlets located in bathroom area shall have GFCI protection. washer. GFCI device shall be located in a readily accessible location. 210.12- All 120 volt outlets located in bedroom areas shall have AFCI protection. Smokes and closet switch. 406.12- All receptacle outlets 15 or 20 amp 120 volt shall be tamper resistant type if installed in or on a dwelling unit. Called contact, no answer, voicemail not set up yet. Left correction notice.
|
ELE16-01628
| Conference | 5/24/2016 | 5/25/2016 | 5/25/2016 8:38:03 AM | A | DONE |
|
|
8 am if possible please to coordinate with other trades Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton Discussed dedicated electrical space for panel boards. Job has been designed with duct work over panel boards limiting dedicated space. As per NEC 110.26(E) area shall be clear width and depth of equipment from floor to 6' above or to structural ceiling. Contractor to explore other locations for panels. Also asked to change egress dor of electrical room to open out and have panic hardware installed.
|