Inspections for the day of: Wednesday, May 25, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02116 ELE-Aging Inspection5/25/20165/25/20165/31/2016 8:02:49 AM CANC
too busy
ELE10-01957 ELE-Aging Inspection5/25/20165/25/20165/31/2016 7:58:39 AM CANC
too busy
ELE16-01283 Final5/25/20165/25/20165/25/2016 2:21:45 PMPFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
110.7 Wiring integrity kitchen lights in-op
406.5 Receptacles shall be rigidly mounted(recept in garage loose)
ELE16-01176 Conference5/24/20165/25/20165/25/2016 1:28:27 PMPPASS
call to set up meeting time with Steve. Phone #: ###-#### Inspection requested via web by steve sellers
EC will provide a equipment grounding conducor with a ear-reaversible crimp to j-box and verify bonding jumper witch looks to established in meter proir to p/s inspection
ELE16-01612 Electrical Rough-In5/25/20165/25/20165/25/2016 12:50:46 PMPPASS
Tenant improvement Phone #: ###-#### Inspection requested via web by Steve Craig
Walls and hard lids in back rooms only ok cover
ELE16-01162 Final5/25/20165/25/20165/25/2016 12:49:47 PMPPASS
Ken Phone #: ###-####
Sign final ok
ELE16-01480 Final5/25/20165/25/20165/25/2016 12:49:16 PMPPASS
Corrections have been made Phone #: ###-#### Inspection requested via web by Matthew White
Downspout was replaced with PVC type, corrections fixed final ok
ELE16-00702 Permanent Service5/24/20165/25/20165/25/2016 10:42:44 AMAPASS
Phone #: ###-#### Inspection requested via web by Celinda Winters
EC will make provision for final that planter in front of main disc. will be flush with top of curb for work space platform. p/s u/g n ok
ELE16-01661 Conference5/24/20165/25/20165/25/2016 9:45:00 AMADONE
Theresa// please call ahead Phone #: ###-####
Discussed code requirements for a detached buidling/ feeding the shop with THHN or UF and GFCI for receptacles in garage and WR in wp outlets. Grounding electrodes to be installed and isolating grounding and grounded conductors in sub panel in garage.
ELE16-00430 Final5/24/20165/25/20165/25/2016 9:02:20 AMAFAIL
Inspection requested via web by steve ragan

314,25 cover required for man hole cover on light pole
ELE16-01413 Final5/24/20165/25/20165/25/2016 8:26:54 AMAPASS
contact is Chad VanOrden at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Final ok