Inspections for the day of: Wednesday, May 25, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00887 INSP-Final Inspection5/24/20165/25/20165/25/2016 4:18:30 PMPFAIL
Head end equipment was verified. Interconnects with the fire sprinkler system were verified. I then did a walk through on the notification devices and noted several at the wrong candella and in one location nine new strobes will need to be added. Several locations have 15cd strobes mounted outside of their listing at 12"-0"
FIR15-00822 INSP-Final Inspection5/25/20165/25/20165/25/2016 4:11:42 PMPFAIL
The interconnects with the fire alarm system tested ok. Forward flush failed.
BLD15-01869 FIRE-Final Inspection5/25/20165/25/20165/25/2016 4:10:27 PMPFAIL
Todays inspection I verified that the exit signs and emergency lights have been repaired/completed
FIR15-00807 INSP-Alarm Testing5/24/20165/25/20165/25/2016 4:05:41 PMPCANC
Overbooked. Rescheduled for tomorrow morning.
BLD16-00332 FIRE-Final Inspection5/25/20165/25/20165/25/2016 10:30:37 AMPCANC
Cancel and reschedule per Jayson Phone #: ###-####
NAF16-00013 INSP-Sprinkler Rough-in/Hydro5/24/20165/25/20165/25/2016 10:25:07 AMPPART
A temporary on this permit only until wireless dialer has been addressed. Also the data sheet for the facp does not match the install. All devices tested through the temp. phone lines.
NAF15-00045 INSP-Final5/24/20165/25/20165/25/2016 10:22:58 AMPPASS
Permit finaled. Forward flush passed.
BLD16-01545 FIRE-Final Inspection5/24/20165/25/20165/25/2016 10:10:58 AMAPART
The south suite, 180, life safety passed. Contractor to provide verification that the south most exit door can be deleted prior to a final sign off.
BLD16-01401 FIRE-Final Inspection5/24/20165/25/20165/25/2016 10:09:50 AMAPASS
Life safety passed. Fire sprinklers and fire alarm not effected and lobby fire extinguishers are adequate.
FIR15-00709 INSP-Conference5/24/20165/25/20165/25/2016 10:05:42 AMADONE
Mike and I spoke about fire rated assemblies and I deferred him to the building inspector
BLD16-01704 FIRE-Final Inspection5/24/20165/25/20165/25/2016 8:12:28 AMAPASS
Life safety passed