GCB15-00125
| FIRE-Final Inspection | 5/24/2016 | 5/25/2016 | 5/25/2016 3:52:45 PM | P | PART |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete with exception to the communicator, current monitoring setup is through phone line, a wireless communicator will take its place once a permit is issued and inspected, fire extinguishers are in place with current inspection tags, Final life fire safety inspection complete with exception to fire alarm communicator, once permit is finaled for communicator the life fire safety can be finaled.
|
GCB15-00116
| FIRE-Final Inspection | 5/24/2016 | 5/25/2016 | 5/25/2016 3:05:10 PM | A | PART |
|
|
TCO allowed per conversation with Scott Arellano, in office/cubicle area's of new addition. A fire sprinkler permit will be needed for transition area between new addition and existing building (Area does have upright protection, pendant heads still in place from ceiling removal) Training room in new addition cannot be occupied until head coverage issue is addressed with partition wall construction, heads will be too far off of partition wall with current head layout.
|
FIR16-00239
| INSP-Sprinkler Rough-in | 5/25/2016 | 5/25/2016 | 5/25/2016 2:07:08 PM | P | CANC |
|
|
Inspection request cancelled per conversation with point of contact, Troy Phone #: ###-####, inspection request will be rescheduled for later date.
|
BLD15-04316
| FIRE-Final Inspection | 5/25/2016 | 5/25/2016 | 5/25/2016 2:03:32 PM | P | PASS |
|
|
FIre sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
FIR16-00316
| INSP-Sprinkler Rough-in | 5/25/2016 | 5/25/2016 | 5/25/2016 1:07:06 PM | P | PART |
|
|
Rough to cover inspection for heads added to offices in and by electronics, notated the city approved drawings with red ink the heads that are approved for cover.
|
FIR15-00398
| INSP-Sprinkler Rough-in/Hydro | 5/24/2016 | 5/25/2016 | 5/25/2016 11:54:39 AM | A | PASS |
|
|
200 psi hydrostatic test complete for underground supply.
|
FIR15-00401
| INSP-Sprinkler Rough-in/Hydro | 5/24/2016 | 5/25/2016 | 5/25/2016 11:53:37 AM | A | PASS |
|
|
200 psi hydrostatic test complete for underground supply.
|
BLD16-00694
| FIRE-Final Inspection | 5/24/2016 | 5/25/2016 | 5/25/2016 10:58:23 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
BLD16-01323
| FIRE-Final Inspection | 5/24/2016 | 5/25/2016 | 5/25/2016 10:41:53 AM | A | PART |
|
|
Life fire safety inspection complete for level 3
|
FIR16-00258
| INSP-Sprinkler Rough-in/Hydro | 5/25/2016 | 5/25/2016 | 5/25/2016 10:20:44 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in basement level complete, basement level approved for cover. 200 psi hydrostatic test complete for basement level.
|
FIR16-00118
| INSP-Sprinkler Rough-in/Hydro | 5/24/2016 | 5/25/2016 | 5/25/2016 10:18:18 AM | A | CANC |
|
|
Inspection request was for basement level, this inspection request cancelled and a new inspection request generated.
|
BLD16-01518
| FIRE-Final Inspection | 5/24/2016 | 5/25/2016 | 5/25/2016 9:42:42 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are in place wirh current inspection tags, door hardware is existing, egress doors have proper hardware, thumbturn deadbolts located on some interior doors. Final life fire safety inspection passed/complete.
|
FIR15-00747
| INSP-Final Inspection | 5/25/2016 | 5/25/2016 | 5/25/2016 9:22:57 AM | A | PART |
|
|
Inspected audio visual devices for firest floor clean room as well as second level clean and dirty mech room. Devices tested today passed/complete.
|