FIR18-00375
| INSP-Sprinkler Rough-in | 5/25/2018 | 5/25/2018 | 5/25/2018 3:30:50 PM | P | PASS |
|
|
Rough to cover inspection for underground supply complete, approved for cover.
|
BLD17-02417
| FIRE-Final Inspection | 5/25/2018 | 5/25/2018 | 5/25/2018 2:17:48 PM | P | PASS |
|
|
Hole next to fire sprinkler head has been filled, final life fire safety inspection complete.
Phone #: ###-#### Inspection requested via web by David Scaggs
|
BLD17-03191
| FIRE-Final Inspection | 5/25/2018 | 5/25/2018 | 5/25/2018 2:00:21 PM | P | PART |
|
|
Final life fire safety inspection complete for TCO in requested area of this permit, fire extinguisher is in place with a current inspection tag, fire alarm and fire sprinkler work to be completed with core and shell remodel, commercial cooking hood operational inspection complete, hood fire alarm interface to completed with core and shell fire alarm inspection. Per conversation with Romeo TCO is authorized for 90 days.
|
FIR18-00332
| INSP-Final Inspection | 5/24/2018 | 5/25/2018 | 5/25/2018 1:58:41 PM | P | PART |
|
|
Operational inspection for ductless hood fire suppression system complete, interface with fire alarm panel will be completed when core and shell fire alarm upgrade is complete. Permit will remain in issued status until fire alarm interface inspection completion.
Dave Phone #: ###-####
|
FIR17-00700
| INSP-Sprinkler Rough-in/Hydro | 5/24/2018 | 5/25/2018 | 5/25/2018 12:47:36 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauges for levels 1 and 2.
Phone #: ###-#### Inspection requested via web by Connie Danes
|
FIR18-00308
| INSP-Sprinkler Rough-in | 5/24/2018 | 5/25/2018 | 5/25/2018 12:30:01 PM | P | PART |
|
|
Rough to cover inspection for riser stub up and approximately 5 feet of underground piping from building footing complete, area installed and inspected approved for cover.
Bryan Collins is the contact for this underground rough-in. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR17-00596
| INSP-Sprinkler Rough-in | 5/25/2018 | 5/25/2018 | 5/25/2018 12:28:19 PM | P | PART |
|
|
Rough to cover inspection for fire sprinkler piping located in operating room 1, OR room 1 is notated on the city approved drawings and is approved for cover (total of 4 heads).
Contact Leroy Anderson - ###-#### 30 Min Prior to RTC Insp Start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
NAF16-00067
| INSP-Final | 5/24/2018 | 5/25/2018 | 5/25/2018 10:44:07 AM | P | DONE |
|
|
Final life fire safety inspection complete.
Call prior to going Phone #: 2087133422 >> Inspection requested via mobile web by Tim Opp
|
NAF16-00066
| INSP-Final | 5/24/2018 | 5/25/2018 | 5/25/2018 10:43:41 AM | P | DONE |
|
|
Final life fire safety inspection complete.
Call prior to going Phone #: 2087133422 >> Inspection requested via mobile web by Tim Opp
|
NAF18-00006
| INSP-Sprinkler Rough-in | 5/24/2018 | 5/25/2018 | 5/25/2018 10:19:51 AM | A | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping located above hardlids, notated cicty approved drawings areas approved for cover.
RICK FRY IS OUR CONTACT Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|
BLD17-04300
| FIRE-Final Inspection | 5/24/2018 | 5/25/2018 | 5/25/2018 8:44:01 AM | A | PASS |
|
|
Fire sprinkler inspection is compete, no fire alarm modifications, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection for area of work complete.
Russ Phone #: ###-####
|
FIR17-00596
| INSP-Sprinkler Rough-in | 5/24/2018 | 5/25/2018 | 5/25/2018 8:42:46 AM | A | CANC |
|
|
Contact Leroy Anderson ###-#### 30 Min Prior to RTC Insp start , please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
FIR18-00175
| INSP-Final Inspection | 5/24/2018 | 5/25/2018 | 5/25/2018 7:33:12 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00060
| INSP-Final Inspection | 5/24/2018 | 5/25/2018 | 5/25/2018 7:32:39 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Sam Ball
|