Inspections for the day of: Friday, May 25, 2018.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-01094 Final5/25/20185/25/20185/25/2018 3:44:20 PMPFAIL
Bj 208 573 0755 Inspection requested via web by william kerwin- no air balance report onsite
MEC18-00790 Final5/22/20185/25/20185/25/2018 3:03:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- co sensors ok
MEC18-01865 Final5/23/20185/25/20185/25/2018 2:38:13 PMPFAIL
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee
- need 1" clearances to b vent going through roof and need insulation sheild to maintain 1" clearances to insulation- Need to seal 4" PVC goose neck- need to support line set on roof
MEC18-02121 Final5/25/20185/25/20185/25/2018 2:12:25 PMPCANC
rtu 4 final at 2 pm ; Phone #: 208- 954
- no acess to building everyone went home early for long weekend
MEC18-02063 Final5/23/20185/25/20185/25/2018 1:49:40 PMPFAIL
1:00 p.m. Greg from Greens will meet you there. Phone #: ###-#### Inspection requested via web by Jerry Crist- 5lb flue pressure test pass- ac fuse ok- need to pull plumbing permit for water before mech permit can be finaled
MEC18-02245 Rough-in5/25/20185/25/20185/25/2018 12:32:16 PMPPASS
3rd floor cover inspection needed please contact Karl at ###-#### with any question''s thank you ###-#### Phone #: ###-#### Inspection requested
via web by Karl Hestekin- 3rd floor ceiling tile cover ok
MEC18-02283 Rough-in5/24/20185/25/20185/25/2018 10:48:01 AMAPART
Shaft inspection please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- 3rd floor mech shaft behind elevator ok- 4th floor and above not ready yet
MEC18-02121 Final5/24/20185/25/20185/25/2018 9:52:09 AMACANC
Phone #: ###-#### Inspection requested via web by Ben Seitz- rescheduled
MEC18-01416 Final5/24/20185/25/20185/25/2018 9:26:05 AMAFAIL
Blast witness 9:30am please.
Questions call Randy ###-#### Phone #: ###-#### Inspection requested via web by Randy Hart- need air balance report onsite for final
MEC18-01416 Conference5/24/20185/25/20185/25/2018 9:24:33 AMAPASS
Blast witness 9:30am please.
Questions call Randy ###-#### Phone #: ###-#### Inspection requested via web by Randy Hart- duct blast pass
MEC18-00800 Final5/24/20185/25/20185/25/2018 8:32:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Oleg Chervak- air balance reports ok- final ok