BLD04-00820
| FIRE-Final Inspection | 5/25/2004 | 5/26/2004 | 5/26/2004 12:00:00 AM | A | FAIL |
|
|
No access to business. Talked to contractor on phone and he is to reschedule for this afternoon 5/26/2004 10:37:41 AM
|
FIR03-00669
| INSP-Sprinkler Rough-in/Hydro | 5/25/2004 | 5/26/2004 | 5/26/2004 12:00:00 AM | A | FAIL |
|
|
backflow preventor was leaking. Hydro test failed 5/26/2004 11:51:47 AM
|
BLD04-00151
| FIRE-Final Inspection | 5/25/2004 | 5/26/2004 | 5/26/2004 12:00:00 AM | A | FAIL |
|
|
Provide emergency light in west exit at north end of store. Provide emergency light near east exit at south end of store. Provide approved hardware on storage room door, both west exterior exit doors and restroom doors 5/26/2004 11:50:50 AM
|
FIR04-00101
| INSP-Final Inspection | 5/26/2004 | 5/26/2004 | 5/26/2004 12:00:00 AM | A | FAIL |
|
|
Provide updated zone map at the facp
|
FIR04-00163
| INSP-Final Inspection | 5/26/2004 | 5/26/2004 | 5/26/2004 12:00:00 AM | A | FAIL |
|
|
Provide ceiling tile around sprinkler heads in storage room
|
FIR02-00005
| INSP-Sprinkler Rough-in | 5/26/2004 | 5/26/2004 | 5/26/2004 12:00:00 AM | P | PART |
|
|
Sprinkler pendants located in area "C" on the second floor west of the sky lights are ok to cover 5/26/2004 3:16:42 PM
|
FIR03-00669
| INSP-Sprinkler Rough-in/Hydro | 5/26/2004 | 5/26/2004 | 5/26/2004 12:00:00 AM | P | PART |
|
|
Hydro test on both wet systems, antifreeze system and the FDC passed. 5/26/2004 4:24:47 PM
|
BLD04-00820
| FIRE-Final Inspection | 5/26/2004 | 5/26/2004 | 5/26/2004 12:00:00 AM | P | FAIL |
|
|
Repair both exit signs to rear exit. Provide emergency lighting for main floor area. Install fire extinguishers as discussed. Provide approved door hardware on all doors including the rear exit. Comply with fire dept. review note #33 5/26/2004 3:22:03 PM
|
FIR04-00288
| INSP-Final Inspection | 5/26/2004 | 5/26/2004 | 5/26/2004 12:00:00 AM | P | PASS |
|
|
Hood suppression system operated correctly 5/26/2004 3:10:32 PM
|