Inspections for the day of: Thursday, May 26, 2005.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01804 Electrical Rough-In5/26/20055/26/20055/26/2005 3:44:16 PMPFAIL
Scheduled by a contractor via Hello! on 5/26/2005 at 8:19:20 AM. Contact: ###-####. met contractor not ready told about 300.4(A)(1)&(D), box fill, light in MB closet, and replace damaged boxes
ELE05-01857 Temporary Service5/26/20055/26/20055/26/2005 3:42:28 PMPPASS
lloyd ###-#### t/s o/h new ok
ELE05-01669 Permanent Service5/12/20055/26/20055/26/2005 2:33:54 PMPPASS
mitch ###-#### p/s o/h rec. ok
ELE05-00904 Final5/26/20055/26/20055/26/2005 1:58:32 PMPFAIL
Scheduled by a contractor via Hello! on 5/26/2005 at 8:58:16 AM. Contact: ###-####. no final structural cor posted states needs shell and core final, before tenant space can be finaled, also 250.119 shall not ID 6 or smaller grd xray equip, 110.2&5
ELE05-00718 Final5/26/20055/26/20055/26/2005 1:16:58 PMAPASS
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok
ELE05-01322 Rough-In Permanent Service5/26/20055/26/20055/26/2005 12:41:37 PMPPASS
Scheduled by a contractor via Hello! on 5/26/2005 at 9:11:33 AM. Contact: ###-####. r/i ok p/s u/g new ok
ELE05-01321 Rough-In Permanent Service5/26/20055/26/20055/26/2005 12:32:19 PMPPASS
Scheduled by a contractor via Hello! on 5/26/2005 at 9:09:36 AM. Contact: ###-####. r/i ok p/s u/g new ok
ELE05-01848 Electrical Rough-In5/25/20055/26/20055/26/2005 11:23:36 AMAFAIL
###-#### - harvey Note: partial for outer wall
not ready make not complete box fill, called left message
ELE05-01846 Permanent Service5/25/20055/26/20055/26/2005 10:57:38 AMAFAIL
don ###-#### cor. posted called 110.26 needs required clearence p/s,200.6 and 250.119 shall not ID 6 or smaller neuts and grds feeder to garage no violations retained, 240.24 no breakers shall be above 6ft 7 inches label panel
ELE05-01822 Temporary Service5/26/20055/26/20055/26/2005 10:26:22 AMAFAIL
5732302 Internet Inspection Request from: Bob Glenn cor t/s needs all debris cleaned from it dirt , wasp nest and so on
ELE05-01823 Temporary Service5/26/20055/26/20055/26/2005 10:24:27 AMAFAIL
5732302 Internet Inspection Request from: Bob Glenn cor drive grd rod flush called
ELE05-01824 Temporary Service5/26/20055/26/20055/26/2005 10:23:36 AMAPASS
5732302 Internet Inspection Request from: Bob Glenn t/s u/g new ok
ELE05-01847 Electrical Rough-In5/25/20055/26/20055/26/2005 10:06:59 AMAFAIL
rob ###-#### cor. posted do not cover, called left message 314.20 outside boxes shall be flush with siding, 300.4(A)(1)(D) nail plates and 11/4" from both inside and outside edges of framing members required,, need correctg address posted at house
ELE05-01387 Final5/25/20055/26/20055/26/2005 9:43:22 AMAFAIL
Scheduled by a contractor via Hello! on 5/25/2005 at 4:23:55 PM. Contact: ###-####. cor. posted called 250.30 (A)(7) FPN and 250.104(D) bond all water systems, 310.15 derate conductors in conduit from panel to jbox and install covers, where is dis
ELE05-01361 Final5/26/20055/26/20055/26/2005 9:12:11 AMAFAIL
Scheduled by a contractor via Hello! on 5/26/2005 at 7:04:02 AM. Contact: ###-####. cor. posted called all wiring for xray equip and room shall comply with 517.
ELE05-01851 Electrical Rough-In5/25/20055/26/20055/26/2005 8:36:43 AMAFAIL
###-#### - mike cor. posted called left message, 210.52(A)&(B) required outlet spacining in great rm N wall, din rm columns define the dinning area, thats wall space
ELE05-00410 ELE-Aging Inspection5/26/20055/26/20055/26/2005 7:31:31 AM DONE
ok
ELE05-00410 Final5/26/20055/26/20055/26/2005 12:00:00 AMPPASS
finaled by 324 on 02-23-05
ELE05-01851 Permanent Service5/26/20055/26/20055/26/2005 12:00:00 AMPPASS
###-#### - mike p/s u/g new ok
ELE05-01669 Final5/26/20055/26/20055/26/2005 12:00:00 AMPPASS
mitch ###-####