BLD05-00497
| FIRE-Final Inspection | 5/25/2005 | 5/26/2005 | 5/26/2005 4:19:44 PM | P | FAIL |
|
|
Final pending repair of one exit sign above the main entry/exit.
|
FIR05-00258
| INSP-Sprinkler Rough-in/Hydro | 5/26/2005 | 5/26/2005 | 5/26/2005 4:07:41 PM | P | PART |
|
|
Overhead hydrostatic test passed inspection. Still need to perform 24 hr. air test.
|
BLD04-00029
| FIRE-Final Inspection | 5/26/2005 | 5/26/2005 | 5/26/2005 4:02:02 PM | P | PASS |
|
|
20th floor passed inspection. Fire life safety finaled.
|
BLD05-00803
| FIRE-Final Inspection | 5/25/2005 | 5/26/2005 | 5/26/2005 1:13:47 PM | P | FAIL |
|
|
Need to install fire extinguisher, verify approved door hardware at storage room and break room, provide approved type remote annunciators for duct smoke detectors.
|
BLD04-00029
| FIRE-Final Inspection | 5/25/2005 | 5/26/2005 | 5/26/2005 10:19:50 AM | A | PART |
|
|
19th floor passed inspection, 20th floor needs max occupant load sign posted in board room.
|
FIR05-00292
| INSP-Final Inspection | 5/25/2005 | 5/26/2005 | 5/26/2005 9:08:54 AM | A | PASS |
|
|
Fire sprinkler passed inspection. Tom D. with Idaho Fire Protection to supply spare SW 20 head in headbox .
|
FIR05-00258
| INSP-Sprinkler Rough-in | 5/26/2005 | 5/26/2005 | 5/26/2005 12:00:00 AM | P | FAIL |
|
|
Provide forward flow apparatus as required by review note #74, provide EQ brace on 4" main north side last piece, provide plans showing two SW heads at overhead door.
|
FIR05-00225
| INSP-Final Inspection | 5/26/2005 | 5/26/2005 | 5/26/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler finaled.
|