ELE05-01561
| ELE-Aging Inspection | 5/26/2006 | 5/26/2006 | 6/2/2006 8:48:44 AM | | DONE |
|
|
called left message, they need to follow up on permits and contact me
|
ELE05-01707
| Final | 5/24/2006 | 5/26/2006 | 5/26/2006 4:11:16 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 5/24/2006 at 9:42:43 AM. Contact: ###-####. called there is no 1700 w westgate
|
ELE06-01927
| Temporary Service | 5/26/2006 | 5/26/2006 | 5/26/2006 3:27:13 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman corr clean dirt from t/s called left message
|
ELE06-00125
| Final | 5/26/2006 | 5/26/2006 | 5/26/2006 2:45:37 PM | P | PART |
|
|
ryan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/o ok card signed
|
ELE05-02785
| Final | 5/26/2006 | 5/26/2006 | 5/26/2006 2:00:50 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 5/26/2006 at 9:28:54 AM. Contact: ###-####. met owner he added stairs needs lighting and 3 ways for them
|
ELE06-00214
| Final | 5/25/2006 | 5/26/2006 | 5/26/2006 1:26:23 PM | A | PASS |
|
|
jamie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE06-00291
| Final | 5/26/2006 | 5/26/2006 | 5/26/2006 12:49:16 PM | P | PASS |
|
|
Chuck; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt p/s ok for final only needs to call in permit for interior wiring for final of office space called left message
|
ELE06-01378
| Rough-In Permanent Service | 5/25/2006 | 5/26/2006 | 5/26/2006 12:33:08 PM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corr. called needs nail plates and complete wiring in dropped ceil areas
|
ELE06-01205
| Rough-In Permanent Service | 5/23/2006 | 5/26/2006 | 5/26/2006 11:43:15 AM | A | FAIL |
|
|
jason appleman; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa Had conference with owner. Did not post correction.
|
ELE05-04252
| Electrical Rough-In | 5/26/2006 | 5/26/2006 | 5/26/2006 10:48:23 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 5/26/2006 at 7:21:43 AM. Contact: ###-####. u/g for sign and flag pole ok
|
ELE05-00462
| Final | 5/23/2006 | 5/26/2006 | 5/26/2006 10:16:53 AM | A | FAIL |
|
|
chad ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie 250.148 grd metal cutin box kit,314.17(B) needs conn for cutin box, 110.3(A) shall replace plastic box damaged back side peninsular counter, 210.52(B) shall install required small appliance branch circuits for kit ,din as code noted states min 2 circuits shall serve countertops outlets 408.4 panel schedule shall match circiut numbers on deadfront and be specfic as to purpose cow reinspection fee called
|
ELE06-00609
| Electrical Rough-In | 5/25/2006 | 5/26/2006 | 5/26/2006 9:12:40 AM | A | PASS |
|
|
ron or al - grid ceiling inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE06-01850
| Temporary Service | 5/26/2006 | 5/26/2006 | 5/26/2006 8:21:33 AM | A | PASS |
|
|
t/s o/h new ok
|
ELE06-01919
| Rough-In Permanent Service | 5/25/2006 | 5/26/2006 | 5/26/2006 8:10:01 AM | A | PASS |
|
|
1st in am for electrode ok p/s o/h rec. ok
|
ELE06-01807
| Electrical Rough-In | 5/25/2006 | 5/26/2006 | 5/26/2006 7:46:08 AM | A | PART |
|
|
Please call Greg to set up a early a.m inspection due to working graveyard shift. Thanks! Greg ###-####; Phone #: ###-#### Internet Inspection Request from: Steve Syltie u/g ok
|