BLD05-02489
| FIRE-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 5:12:32 PM | A | FAIL |
|
|
The project related fire sprinkler and alarm permits must be inspected and approved prior to life safety final approval. Informed general contractor of requirements and advised him to read the building permit fire code review notes and pretest before next inspection.
|
FIR06-00247
| INSP-Final Inspection | 5/26/2006 | 5/26/2006 | 5/26/2006 5:07:10 PM | P | FAIL |
|
|
HVAC units were not in a condition to allow testing of the duct smoke detectors (T-stats not installed), FACP currently in alarm due to ansul system testing, fire sprinkler riser devices not tested as sprinkler contractor has correction items to address, discussed some previously noted issues with alarm contractor including a/v spacing, back boxes, manual pulls, and as-builts. Due to conditions of the project no final inspection could be performed, requested contractor to reschedule when ready for final, also noted that EOL's have changed from approved plans.
|
FIR06-00387
| INSP-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 4:50:36 PM | A | PASS |
|
|
The hood suppression system functioned properly under test conditions, the provided K class extinguisher to be mounted on the wall as discussed.
|
FIR06-00146
| INSP-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 4:48:23 PM | A | FAIL |
|
|
The DP in the east side cooler is blocked by a surface mounted fan cooling unit, one head in the east dining area directly in front of a heat diffuser needs to be intermediate temp. rating, missing escutcheon at kitchen hallway east exit, provide signage for antifreeze riser, provide 200 deg. ssu for the head box, still need to test sprinkler related alarms and tampers at the riser.
|
BLD06-00324
| FIRE-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 2:32:53 PM | A | NR |
|
|
No inspection done, the project related fire sprinkler permit must be requested for final inspection and approval before BLD life safety final can be granted.
|
BLD06-00322
| FIRE-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 2:29:59 PM | A | FAIL |
|
|
The project related fire sprinkler permit must be requested for final inspection and approval prior to BLD life safety final, missing door hardware at the glass doors, confrence room doors are not installed yet, temporary emergency lights are installed at this time. Informed contractor that only a "partial" could be given if permanent lighting was not in place including emergency lights.
|
FIR06-00264
| INSP-Final Inspection | 5/26/2006 | 5/26/2006 | 5/26/2006 2:22:22 PM | P | PASS |
|
|
Fire alarm passed field inspection, permit finaled.
|
BLD06-00401
| FIRE-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 12:10:26 PM | A | PASS |
|
|
Items on correction notice have been completed, fire life safety inspection passed. Note: door hardware at some locations is not installed-verified hardware on site and per door schedule is okay, final approval at structural inspection.
|
BLD05-03440
| FIRE-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 11:43:31 AM | A | FAIL |
|
|
Door assembly at the 2-hour rated exit enclosure does not meet requirements, door from the workroom to the gift shop needs adjustment, HVAC register is completely blocked by a wooden cabinet, notified contractor the approved plans and review comments are to be available at the next inspection.
|
BLD06-00322
| FIRE-Alarm Testing | 5/25/2006 | 5/26/2006 | 5/26/2006 11:08:00 AM | A | DEFR |
|
|
Duplicate inspection request already called in.
|
BLD05-02991
| FIRE-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 10:49:04 AM | A | FAIL |
|
|
The project appears satisfactory, however the approved plans, permit card, inspection record and review notes were not available on site for verification. Notified contractor to provide the correct documentation and reschedule inspection.
|
MIS06-00091
| FIR-Final | 5/25/2006 | 5/26/2006 | 5/26/2006 10:02:13 AM | A | FAIL |
|
|
Need to provide approved hardware at the side door exit as discussed and per note #2 on review documents, NO storage allowed in the basement, post max occupant load sign as red lined on plan.
|
BLD06-00513
| FIRE-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 9:59:06 AM | A | PASS |
|
|
Fire life safety inspection passed.
|
BLD06-00011
| FIRE-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 12:00:00 AM | A | PASS |
|
|
andy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
FIR06-00380
| INSP-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 12:00:00 AM | A | PART |
|
|
david ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Ready for ceiling tiles in place and adjustment of head in new office next to sink area.
|
FIR06-00206
| INSP-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/25/2006 at 2:45:58 PM. Contact: ###-####.
|
FIR06-00207
| INSP-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/25/2006 at 2:48:08 PM. Contact: ###-####.
|
FIR06-00208
| INSP-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/25/2006 at 2:49:18 PM. Contact: ###-####.
|
FIR06-00144
| INSP-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 12:00:00 AM | A | PASS |
|
|
Contact: Todd; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
Sprinkler Inspection card is missing.
|
FIR06-00356
| INSP-Sprinkler Rough-in | 5/25/2006 | 5/26/2006 | 5/26/2006 12:00:00 AM | A | PASS |
|
|
steve - cover insp; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
OK to cover. Prior to final, check for 2" main and line pipe heat tape and wrap removal.
|
FIR06-00324
| INSP-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 5/25/2006 at 2:06:13 PM. Contact: ###-####.
Fire Alarm NAC ckt acceptable.
|