Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-02489 FIRE-Final Inspection5/25/20065/26/20065/26/2006 5:12:32 PMAFAIL
The project related fire sprinkler and alarm permits must be inspected and approved prior to life safety final approval. Informed general contractor of requirements and advised him to read the building permit fire code review notes and pretest before next inspection.
FIR06-00247 INSP-Final Inspection5/26/20065/26/20065/26/2006 5:07:10 PMPFAIL
HVAC units were not in a condition to allow testing of the duct smoke detectors (T-stats not installed), FACP currently in alarm due to ansul system testing, fire sprinkler riser devices not tested as sprinkler contractor has correction items to address, discussed some previously noted issues with alarm contractor including a/v spacing, back boxes, manual pulls, and as-builts. Due to conditions of the project no final inspection could be performed, requested contractor to reschedule when ready for final, also noted that EOL's have changed from approved plans.
FIR06-00387 INSP-Final Inspection5/25/20065/26/20065/26/2006 4:50:36 PMAPASS
The hood suppression system functioned properly under test conditions, the provided K class extinguisher to be mounted on the wall as discussed.
FIR06-00146 INSP-Final Inspection5/25/20065/26/20065/26/2006 4:48:23 PMAFAIL
The DP in the east side cooler is blocked by a surface mounted fan cooling unit, one head in the east dining area directly in front of a heat diffuser needs to be intermediate temp. rating, missing escutcheon at kitchen hallway east exit, provide signage for antifreeze riser, provide 200 deg. ssu for the head box, still need to test sprinkler related alarms and tampers at the riser.
BLD06-00324 FIRE-Final Inspection5/25/20065/26/20065/26/2006 2:32:53 PMANR
No inspection done, the project related fire sprinkler permit must be requested for final inspection and approval before BLD life safety final can be granted.
BLD06-00322 FIRE-Final Inspection5/25/20065/26/20065/26/2006 2:29:59 PMAFAIL
The project related fire sprinkler permit must be requested for final inspection and approval prior to BLD life safety final, missing door hardware at the glass doors, confrence room doors are not installed yet, temporary emergency lights are installed at this time. Informed contractor that only a "partial" could be given if permanent lighting was not in place including emergency lights.
FIR06-00264 INSP-Final Inspection5/26/20065/26/20065/26/2006 2:22:22 PMPPASS
Fire alarm passed field inspection, permit finaled.
BLD06-00401 FIRE-Final Inspection5/25/20065/26/20065/26/2006 12:10:26 PMAPASS
Items on correction notice have been completed, fire life safety inspection passed. Note: door hardware at some locations is not installed-verified hardware on site and per door schedule is okay, final approval at structural inspection.
BLD05-03440 FIRE-Final Inspection5/25/20065/26/20065/26/2006 11:43:31 AMAFAIL
Door assembly at the 2-hour rated exit enclosure does not meet requirements, door from the workroom to the gift shop needs adjustment, HVAC register is completely blocked by a wooden cabinet, notified contractor the approved plans and review comments are to be available at the next inspection.
BLD06-00322 FIRE-Alarm Testing5/25/20065/26/20065/26/2006 11:08:00 AMADEFR
Duplicate inspection request already called in.
BLD05-02991 FIRE-Final Inspection5/25/20065/26/20065/26/2006 10:49:04 AMAFAIL
The project appears satisfactory, however the approved plans, permit card, inspection record and review notes were not available on site for verification. Notified contractor to provide the correct documentation and reschedule inspection.
MIS06-00091 FIR-Final5/25/20065/26/20065/26/2006 10:02:13 AMAFAIL
Need to provide approved hardware at the side door exit as discussed and per note #2 on review documents, NO storage allowed in the basement, post max occupant load sign as red lined on plan.
BLD06-00513 FIRE-Final Inspection5/25/20065/26/20065/26/2006 9:59:06 AMAPASS
Fire life safety inspection passed.
BLD06-00011 FIRE-Final Inspection5/25/20065/26/20065/26/2006 12:00:00 AMAPASS
andy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
FIR06-00380 INSP-Final Inspection5/25/20065/26/20065/26/2006 12:00:00 AMAPART
david ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Ready for ceiling tiles in place and adjustment of head in new office next to sink area.
FIR06-00206 INSP-Final Inspection5/25/20065/26/20065/26/2006 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 5/25/2006 at 2:45:58 PM. Contact: ###-####.
FIR06-00207 INSP-Final Inspection5/25/20065/26/20065/26/2006 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 5/25/2006 at 2:48:08 PM. Contact: ###-####.
FIR06-00208 INSP-Final Inspection5/25/20065/26/20065/26/2006 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 5/25/2006 at 2:49:18 PM. Contact: ###-####.
FIR06-00144 INSP-Final Inspection5/25/20065/26/20065/26/2006 12:00:00 AMAPASS
Contact: Todd; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
Sprinkler Inspection card is missing.
FIR06-00356 INSP-Sprinkler Rough-in5/25/20065/26/20065/26/2006 12:00:00 AMAPASS
steve - cover insp; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
OK to cover. Prior to final, check for 2" main and line pipe heat tape and wrap removal.
FIR06-00324 INSP-Final Inspection5/25/20065/26/20065/26/2006 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 5/25/2006 at 2:06:13 PM. Contact: ###-####.

Fire Alarm NAC ckt acceptable.