Inspections for the day of: Tuesday, May 26, 2009.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-00850 Final5/26/20095/26/20095/26/2009 3:39:02 PMPPASS
Final on permanent service. ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher
ELE09-00252 Final5/26/20095/26/20095/26/2009 3:38:42 PMPPASS
Kim Phone #: ###-#### ok
ELE09-00102 Final5/26/20095/26/20095/26/2009 2:34:24 PMPPASS
Sean Phone #: ###-####
ELE09-00891 Electrical Rough-In5/26/20095/26/20095/26/2009 1:46:42 PMPPART
cover for walls only please-Shane Phone #: ###-#### walls and rest rm hard ceiling
ELE09-00786 Final5/22/20095/26/20095/26/2009 1:11:15 PMPPASS
Mark Phone #: ###-####
ELE09-00786 Permanent Service5/26/20095/26/20095/26/2009 1:10:53 PMPPASS
p/s o/h rec. ok
ELE09-00894 Final5/26/20095/26/20095/26/2009 10:27:26 AMAFAIL
Call for access ahead of time. Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called needs grding and bonding , 4 wire feed to range
ELE09-00853 Permanent Service5/22/20095/26/20095/26/2009 10:02:10 AMAFAIL
clyde Phone #: ###-#### called left message no grd to water, and no access to house
ELE09-00102 Final5/24/20095/26/20095/26/2009 9:11:15 AMAFAIL
please renspect, thank you Phone #: ###-#### Internet Inspection Request from: Sean Peltier no power to 1/2 of basement, called
ESC09-00111 General Inspection5/26/20095/26/20095/26/2009 8:31:27 AMAPASS
ok
ELE09-00890 Rough-In Permanent Service5/22/20095/26/20095/26/2009 8:30:54 AMAFAIL
Dino Phone #: ###-#### called corr. 210.52(A&C) needs receps for wall space fixed panel patio door and countertop in din rm 334.23 protect all cables 6ft of attic access, 314.17&362.6 bushings for cables, and conn for ENT at low voltage cabinet