Inspections for the day of: Wednesday, May 26, 2010.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00331 FIR-Aging Inspection5/26/20105/26/20106/3/2010 11:28:30 AM NR
I spoke to Don and he going to follow up on job status and call me back. A follow up inspection has been scheduled for next week,
FIR03-00510 INSP-Conference5/19/20105/26/20105/27/2010 8:16:32 AMADONE
Left voice mail for Bob at Oxard requesting project status. Phone ###-#### #110
FIR04-00375 INSP-Conference5/19/20105/26/20105/27/2010 8:16:17 AMADONE
Left voice mail for Bob at Oxard requesting project status. Phone ###-#### #110
FIR04-00374 INSP-Conference5/19/20105/26/20105/27/2010 8:16:01 AMADONE
Left voice mail for Bob at Oxard requesting project status. Phone ###-#### #110
FIR03-00381 INSP-Conference5/19/20105/26/20105/27/2010 8:15:45 AMADONE
Left voice mail for Bob at Oxard requesting project status. Phone ###-#### #110
BLD09-00557 FIRE-Final Inspection5/26/20105/26/20105/27/2010 7:46:07 AMPCANC
Wrong inspection type called in. Herb needed fire alarm inspection.
BLD10-00415 FIRE-Final Inspection5/26/20105/26/20105/26/2010 4:29:49 PMPPASS
Life safety passed. The thumbturn lock on the east door will be removed prior to the building inspection
FIR09-00673 INSP-Final Inspection5/26/20105/26/20105/26/2010 2:01:43 PMPPASS
Permit finaled.
BLD09-00077 FIRE-Final Inspection5/25/20105/26/20105/26/2010 1:54:55 PMAPASS
Life safety passed.
BLD10-00912 FIRE-Final Inspection5/25/20105/26/20105/26/2010 1:53:59 PMAPASS
Life safety passed.
FIR09-00535 INSP-Sprinkler Rough-in/Hydro5/24/20105/26/20105/26/2010 12:41:38 PMAPASS
Jeff is looking for the original correction list. If all items have been met on that list then the remaining items are the signage as discussed and copies of the test papers.
FIR10-00060 INSP-Alarm Testing5/25/20105/26/20105/26/2010 12:22:52 PMADONE
The items previously listed have been corrected. Duct smoke detectors have been tested for hvac shutdown. EOL voltage was verified. Two smoke detectors were tested for operation that operate roll down fire doors. They were not approved for location only for function. They are not shown on the city approved plans. They are to be included on the revised plans. Items remaining for phase I include the 135cd strobe and the repair of the corridor roll down fire door.
FIR09-00707 INSP-Final Inspection5/25/20105/26/20105/26/2010 12:19:04 PMAFAIL
The alarm interconnection for the devices located in phase I were tested today. It appears the only outstanding item for phase I is the forward flush failed.
FIR10-00118 INSP-Final Inspection5/25/20105/26/20105/26/2010 12:17:19 PMAPASS
The hood suppression system operated correctly. Permit finaled.
BLD09-01611 FIRE-Final Inspection5/25/20105/26/20105/26/2010 12:15:37 PMAPASS
Revised drawings have been provided and approved which show the new fire hydrant being deleted. Life safety passed.