Inspections for the day of: Tuesday, May 26, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00931 ELE-Aging Inspection5/26/20155/26/20155/29/2015 2:22:06 PM DONE
left another message
ELE15-01520 Temporary Service5/26/20155/26/20155/26/2015 4:06:34 PMPPASS
temp pole Phone #: ###-#### Inspection requested via web by Stephen Kren t/s o/h n ok NOTE; I LET CONTRACTOR KNOW METER NEEDS TO BE 5 ' 6" to center + or - 6" from now on
ELE12-02746 Final5/22/20155/26/20155/26/2015 2:52:15 PMAFAIL
Any questions get ahold of Tony Young 332.12- nm cable subject to physical damage needs sleeve to furnace.
GCE15-00040 GCE-Final5/26/20155/26/20155/26/2015 2:08:31 PMPFAIL
Terry ###-#### too many items to list not ready
ELE15-00561 Final5/26/20155/26/20155/26/2015 1:06:09 PMAPASS
Inspection requested via web by Mike Swift final ok ceilings included
ELE14-03488 Permanent Service5/25/20155/26/20155/26/2015 12:30:59 PMAFAIL
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 250.68-Install nuetral disconnect link or bonding jumper for nuetral at main disconnect. 110.24- fault currents need to be labeled with date from Idaho Power on main disconnect. 110.16-arc flash warning label required on panels and main. Slip joint coupling required on secondary underground conduit with sch 80 conduit. Install bonding bushing at main disconnect.
ELE15-00169 Electrical Rough-In5/22/20155/26/20155/26/2015 11:38:29 AMANR
steve hook is contact, ###-####, 1st and 2nd floor final. Phone #: ###-#### Inspection requested via web by Debby Pierce partial final on 1st floor needs missing covers and lost nuetral in south office receptacles
ELE15-00900 Final5/21/20155/26/20155/26/2015 10:52:43 AMAPASS
I would like an inspection for ground bushing at panel to be completed at 12:00 PM. because of Idaho Power. Phone #: ###-#### Inspection requested via web by Kevin Koomler ground bushing installed final ok
ELE15-01518 Final5/25/20155/26/20155/26/2015 10:20:40 AMANR
call for access. Phone #: ###-#### Inspection requested via web by michael hunt not ready for final need 2 pole breaker and threaded connection for intersystem bond and label directory
ELE15-01518 Permanent Service5/26/20155/26/20155/26/2015 10:11:05 AMPPASS
call for access. Phone #: ###-#### Inspection requested via web by michael hunt p/s o/h rec ok upgraded from 100amp to 200 amp
ELE14-03316 Electrical Rough-In5/22/20155/26/20155/26/2015 9:09:56 AMAPASS
Contact Tpm Hartung for level 1 garage roof deck rough in. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok parking ceiling orange area