Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02998 ELE-Aging Inspection5/26/20165/26/20165/27/2016 3:23:11 PM PASS
Waiting on owner. Fees will be assessed in future
ELE16-00329 Final5/26/20165/26/20165/26/2016 3:24:41 PMPCANC
Partial Final - Walk thru 3rd and 4th floor Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Rescheduled
ELE16-00329 Electrical Rough-In5/26/20165/26/20165/26/2016 3:21:41 PMPPASS
Basement Ceiling Phone #: ###-#### Inspection requested via web by Kerri Hamilton Basement grid rough in ok cover. 2 room not accessible to to secure areas will check in future.
ELE16-00992 Final5/25/20165/26/20165/26/2016 2:26:31 PMPFAIL
Electrician onsite is Asher Sears. 12th floor. Suite 1201 Phone #: ###-#### Inspection requested via web by steve ragan
314.25- All boxes shall have covers. Covers off for painting.
408.4- Circuit directory shall be complete/
ELE16-00303 Electrical Rough-In5/26/20165/26/20165/26/2016 2:21:00 PMPPASS
BSU TI stairway. 3rd floor ceiling for cover. Contact is Eric Gibson 871 -1363 Phone #: ###-#### Inspection requested via web by Toby Groves
discussed door location in 2nd floor electrical room. With 45" width to get to door Chief Electrical inspector ruled unobstructed egress to door was sufficient. Grid 3rd floor stairway rough in ok cover. Book not at desk to mark as inspected.
ELE15-03377 Final5/26/20165/26/20165/26/2016 12:55:47 PMPPASS
Contact is Tom. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Final ok
ELE16-00904 Final5/25/20165/26/20165/26/2016 12:42:51 PMPPASS
Call for Access Phone #: ###-#### Inspection requested via web by steve sellers Final ok
ELE16-00523 Final5/26/20165/26/20165/26/2016 11:17:44 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
110.3- Device shall be wired as per instructions. Miswire laundry GFCI, will not set and others not working.
210.52(D)- Bathroom receptacle location shall be on wall or prtition ajacent to basin or basin counter top. Jack and Jill bathroom receptacle located in cabinet.1 shall be installed on side of cabinet or wall.
324.20- Box mounted in wall with wood covering shall be flush or have extension ring installed in master bath cabinet.
ELE16-01547 Final5/25/20165/26/20165/26/2016 10:13:14 AMAPASS
Phone #: ###-#### Inspection requested via web by Daniel Schaffeld
Changed from newon to LED. Final ok
ELE16-00942 Final5/25/20165/26/20165/26/2016 9:10:20 AMAFAIL
Lockbox 02468, if you have any questions, please call Jake ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
314.20- Boxes installed in wall with combustable covering shall be flush or have extension rings installed. 3 receptacles in nook wains coating.
ELE16-01283 Final5/25/20165/26/20165/26/2016 8:26:13 AMANH
Phone #: ###-#### Inspection requested via web by Darryn Coburn
House locked no garage door key pad. called for key location left message.
ELE16-01838 Electrical Rough-In5/26/20165/26/20165/26/2016 12:00:00 AMAPASS
Rm 808, 807 Phone #: ###-#### Inspection requested via web by Tom Betty
Walls in rooms noted rough in ok cover