ELE12-02998
| ELE-Aging Inspection | 5/26/2016 | 5/26/2016 | 5/27/2016 3:23:11 PM | | PASS |
|
|
Waiting on owner. Fees will be assessed in future
|
ELE16-00329
| Final | 5/26/2016 | 5/26/2016 | 5/26/2016 3:24:41 PM | P | CANC |
|
|
Partial Final - Walk thru 3rd and 4th floor Phone #: ###-#### Inspection requested via web by Kerri Hamilton Rescheduled
|
ELE16-00329
| Electrical Rough-In | 5/26/2016 | 5/26/2016 | 5/26/2016 3:21:41 PM | P | PASS |
|
|
Basement Ceiling Phone #: ###-#### Inspection requested via web by Kerri Hamilton Basement grid rough in ok cover. 2 room not accessible to to secure areas will check in future.
|
ELE16-00992
| Final | 5/25/2016 | 5/26/2016 | 5/26/2016 2:26:31 PM | P | FAIL |
|
|
Electrician onsite is Asher Sears. 12th floor. Suite 1201 Phone #: ###-#### Inspection requested via web by steve ragan 314.25- All boxes shall have covers. Covers off for painting. 408.4- Circuit directory shall be complete/
|
ELE16-00303
| Electrical Rough-In | 5/26/2016 | 5/26/2016 | 5/26/2016 2:21:00 PM | P | PASS |
|
|
BSU TI stairway. 3rd floor ceiling for cover. Contact is Eric Gibson 871 -1363 Phone #: ###-#### Inspection requested via web by Toby Groves discussed door location in 2nd floor electrical room. With 45" width to get to door Chief Electrical inspector ruled unobstructed egress to door was sufficient. Grid 3rd floor stairway rough in ok cover. Book not at desk to mark as inspected.
|
ELE15-03377
| Final | 5/26/2016 | 5/26/2016 | 5/26/2016 12:55:47 PM | P | PASS |
|
|
Contact is Tom. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Final ok
|
ELE16-00904
| Final | 5/25/2016 | 5/26/2016 | 5/26/2016 12:42:51 PM | P | PASS |
|
|
Call for Access Phone #: ###-#### Inspection requested via web by steve sellers Final ok
|
ELE16-00523
| Final | 5/26/2016 | 5/26/2016 | 5/26/2016 11:17:44 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3- Device shall be wired as per instructions. Miswire laundry GFCI, will not set and others not working. 210.52(D)- Bathroom receptacle location shall be on wall or prtition ajacent to basin or basin counter top. Jack and Jill bathroom receptacle located in cabinet.1 shall be installed on side of cabinet or wall. 324.20- Box mounted in wall with wood covering shall be flush or have extension ring installed in master bath cabinet.
|
ELE16-01547
| Final | 5/25/2016 | 5/26/2016 | 5/26/2016 10:13:14 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Daniel Schaffeld Changed from newon to LED. Final ok
|
ELE16-00942
| Final | 5/25/2016 | 5/26/2016 | 5/26/2016 9:10:20 AM | A | FAIL |
|
|
Lockbox 02468, if you have any questions, please call Jake ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan 314.20- Boxes installed in wall with combustable covering shall be flush or have extension rings installed. 3 receptacles in nook wains coating.
|
ELE16-01283
| Final | 5/25/2016 | 5/26/2016 | 5/26/2016 8:26:13 AM | A | NH |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn House locked no garage door key pad. called for key location left message.
|
ELE16-01838
| Electrical Rough-In | 5/26/2016 | 5/26/2016 | 5/26/2016 12:00:00 AM | A | PASS |
|
|
Rm 808, 807 Phone #: ###-#### Inspection requested via web by Tom Betty Walls in rooms noted rough in ok cover
|