BLD15-04346
| BLD-Conference | 5/25/2016 | 5/26/2016 | 5/26/2016 2:29:36 PM | P | CANC |
|
|
|
BLD16-01209
| FIRE-Final Inspection | 5/25/2016 | 5/26/2016 | 5/26/2016 2:13:04 PM | P | PASS |
|
|
life safety passed
|
FIR16-00353
| INSP-Final Inspection | 5/26/2016 | 5/26/2016 | 5/26/2016 2:11:34 PM | P | PASS |
|
|
permit finaled
|
FIR15-00909
| INSP-Sprinkler Rough-in | 5/26/2016 | 5/26/2016 | 5/26/2016 1:47:42 PM | P | PASS |
|
|
The two pieces of 10" underground supply piping from the previously approved stub out heading towards the street are ok to cover.
|
FIR16-00131
| INSP-Sprinkler Rough-in | 5/26/2016 | 5/26/2016 | 5/26/2016 1:23:37 PM | P | PASS |
|
|
See the city approved plans for two pendant heads on the upper level that are ok for cover.
|
FIR16-00249
| INSP-Final Inspection | 5/25/2016 | 5/26/2016 | 5/26/2016 12:11:52 PM | A | PASS |
|
|
Permit finaled
|
FIR16-00104
| INSP-Supply line flush | 5/26/2016 | 5/26/2016 | 5/26/2016 10:58:22 AM | P | PASS |
|
|
Underground supply line flush passed.
|
FIR16-00282
| INSP-Supply line flush | 5/26/2016 | 5/26/2016 | 5/26/2016 10:54:21 AM | P | CANC |
|
|
Wrong permit number called in for underground flush
|
FIR16-00334
| INSP-Final Inspection | 5/25/2016 | 5/26/2016 | 5/26/2016 10:53:36 AM | A | PASS |
|
|
Permit finaled
|
BLD16-01311
| FIRE-Final Inspection | 5/25/2016 | 5/26/2016 | 5/26/2016 10:21:13 AM | A | PASS |
|
|
Life safety passed
|
BLD15-01869
| FIRE-Conference | 5/26/2016 | 5/26/2016 | 5/26/2016 10:01:10 AM | P | DONE |
|
|
For a final sign off the project related fire alarm and fire sprinkler permits need addressed. Fire alarm plans need resubmitted and notification tested. Fire sprinkler forward flow is only proving half of the required water for the system. For life safety the signage needs to be provided as discussed for the Oil Storage room.
|
FIR15-00887
| INSP-Final Inspection | 5/26/2016 | 5/26/2016 | 5/26/2016 9:58:56 AM | A | FAIL |
|
|
Duct smoke detectors have been tested. To final this permit plan modifications will be required for the additional NAC panel and associated horn/strobes and then of course the testing of these devices.
|
FIR16-00272
| INSP-Alarm Testing | 5/26/2016 | 5/26/2016 | 5/26/2016 7:42:26 AM | A | PASS |
|
|
See the city approved drawings for devices marked "ok" that have been tested.
|