Inspections for the day of: Thursday, May 26, 2016.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-04346 BLD-Conference5/25/20165/26/20165/26/2016 2:29:36 PMPCANC
BLD16-01209 FIRE-Final Inspection5/25/20165/26/20165/26/2016 2:13:04 PMPPASS
life safety passed
FIR16-00353 INSP-Final Inspection5/26/20165/26/20165/26/2016 2:11:34 PMPPASS
permit finaled
FIR15-00909 INSP-Sprinkler Rough-in5/26/20165/26/20165/26/2016 1:47:42 PMPPASS
The two pieces of 10" underground supply piping from the previously approved stub out heading towards the street are ok to cover.
FIR16-00131 INSP-Sprinkler Rough-in5/26/20165/26/20165/26/2016 1:23:37 PMPPASS
See the city approved plans for two pendant heads on the upper level that are ok for cover.
FIR16-00249 INSP-Final Inspection5/25/20165/26/20165/26/2016 12:11:52 PMAPASS
Permit finaled
FIR16-00104 INSP-Supply line flush5/26/20165/26/20165/26/2016 10:58:22 AMPPASS
Underground supply line flush passed.
FIR16-00282 INSP-Supply line flush5/26/20165/26/20165/26/2016 10:54:21 AMPCANC
Wrong permit number called in for underground flush
FIR16-00334 INSP-Final Inspection5/25/20165/26/20165/26/2016 10:53:36 AMAPASS
Permit finaled
BLD16-01311 FIRE-Final Inspection5/25/20165/26/20165/26/2016 10:21:13 AMAPASS
Life safety passed
BLD15-01869 FIRE-Conference5/26/20165/26/20165/26/2016 10:01:10 AMPDONE
For a final sign off the project related fire alarm and fire sprinkler permits need addressed. Fire alarm plans need resubmitted and notification tested. Fire sprinkler forward flow is only proving half of the required water for the system. For life safety the signage needs to be provided as discussed for the Oil Storage room.
FIR15-00887 INSP-Final Inspection5/26/20165/26/20165/26/2016 9:58:56 AMAFAIL
Duct smoke detectors have been tested. To final this permit plan modifications will be required for the additional NAC panel and associated horn/strobes and then of course the testing of these devices.
FIR16-00272 INSP-Alarm Testing5/26/20165/26/20165/26/2016 7:42:26 AMAPASS
See the city approved drawings for devices marked "ok" that have been tested.