Inspections for the day of: Tuesday, May 26, 2020.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00311 Conference5/26/20205/26/20205/26/2020 2:37:17 PMPFAIL
We need to confer with inspector prior to installing owner supplied lighting fixtures. Please call Jeff ###-####. Phone #: ###-#### Inspection requested via web by Joe McLean Looked at luminaires and all packaging, unable to locate a listing accepted by the US.
110.3(B)- All electrical equipment shall be tested and approved by an acceptable testing company. These luminaires are not to be installed unless field evaluated and approved prior to installation. Photos of packaging and instructions taken.
ELE19-04799 Conference5/26/20205/26/20205/26/2020 1:47:28 PMPPASS
Discuss bonding at pool shell area. Rebar in structural concrete (not pool) to utilize epoxy coated rebar Phone #: ###-#### Inspection requested via web by Jason Parke
Called and discussed if an epoxy covered rebar is used below pool shell, question about bonding.
680.26(B)(3)- A rebar encapsulated in a non-conductive covering shall not be required to be bonded.
ELE20-01749 Temporary Service5/22/20205/26/20205/26/2020 11:57:24 AMAPASS
temp pole Phone #: ###-#### Inspection requested via web by kevin blackmon t/s u/g n ok
ELE20-01629 Rough-In Permanent Service5/22/20205/26/20205/26/2020 11:37:11 AMAPASS
Phone #: ###-#### Inspection requested via web by Troy Ballard
Rough in ok cover p/s u/g n ok
ELE20-00504 Final5/22/20205/26/20205/26/2020 10:18:35 AMAFAIL
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard
110.3- Items not working, Mini-split over current device not in, bathroom receptacles not working, master bed paddle fan switch not working.
200.7- white conductors used for other than grounded conductors shall be identified other than white. Mini- split, AC.
ELE20-01158 Electrical Rough-In5/22/20205/26/20205/26/2020 9:25:18 AMAPASS
Rough - in please. Thank you. Blessings!
Phone #: ###-#### Inspection requested via web by Kyle Lott
Will need to verify light and receptacle in attic for HVAC equipment.
East addition ceiling rough in ok cover.