Inspections for the day of: Tuesday, May 27, 2003.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00072 FIR-Aging Inspection5/27/20035/27/20035/27/2003 12:00:00 AM NR
I spoke to George with Treasure Valley Fire Protection and he stated he would follow up with his people and get the inspection called in if the work had been completed 5/27/2003 1:34:29 PM
FIR02-00476 INSP-Final Inspection5/20/20035/27/20035/27/2003 12:00:00 AMAFAIL
Provide updated map, provide immediate shutdown for the two new hvac units in the waiting area, provide sync for the strobes and temporal for the horns in the new/remodeled areas. Provide nfpa 72 forms 5/27/2003 9:05:48 AM
BLD03-00776 FIRE-Final Inspection5/23/20035/27/20035/27/2003 12:00:00 AMAPASS
Fire life safety is OK. Door hardware was not installed yet but what the contractor showed me in the boxes would be OK 5/27/2003 9:47:18 AM
FIR01-00462 INSP-Sprinkler Rough-in/Hydro5/23/20035/27/20035/27/2003 12:00:00 AMPPASS
mike; Phone #: ###-#### Hydro test for the entire wet system is OK. This test included the attic dry system 5/27/2003 3:04:40 PM
FIR03-00242 INSP-Conference5/27/20035/27/20035/27/2003 12:00:00 AMPPASS
Underground supply piping is ok to cover 5/27/2003 4:06:06 PM
BLD03-00673 FIRE-Final Inspection5/27/20035/27/20035/27/2003 12:00:00 AMPPASS
gil; Phone #: ###-#### Life safety finaled 5/27/2003 3:05:24 PM
BLD02-02620 FIRE-Final Inspection5/27/20035/27/20035/27/2003 12:00:00 AMPPASS
###-#### Fire life safety, fire sprinkler and fire alarm finaled 5/27/2003 4:07:33 PM