BLD04-00820
| FIRE-Final Inspection | 5/26/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | A | PART |
|
|
A temporary occupancy was given with dave millers permission until the fire alarm plans have been approved and work completed for the duct smoke detector addition. The unit in question is rated for 4000 cfm. 5/27/2004 8:25:51 AM
|
BLD04-00820
| FIRE-Final Inspection | 5/26/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | A | PART |
|
|
A temporary occupancy was given with dave millers permission until the fire alarm plans have been approved and work completed for the duct smoke detector addition. The unit in question is rated for 4000 cfm. 5/27/2004 8:25:51 AM
|
FIR04-00318
| INSP-Sprinkler Rough-in/Hydro | 5/26/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 5/27/2004 9:00:27 AM
|
BLD04-00151
| FIRE-Final Inspection | 5/26/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 5/27/2004 10:40:34 AM
|
BLD04-00372
| FIRE-Final Inspection | 5/26/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | A | FAIL |
|
|
Provide approved door hardware on all doors in remodeled area. Relocate fire extinguisher to the T.I. space. Repair the existing exit sign. The two hvac units require duct smoke detectors for automatic shutdown. See review note #18. 5/27/2004 10:25:42 AM
|
FIR04-00318
| INSP-Final Inspection | 5/27/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | A | PASS |
|
|
fire sprinkler finaled
|
FIR04-00163
| INSP-Final Inspection | 5/27/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | A | PASS |
|
|
fire sprinklers finaled
|
FIR04-00101
| INSP-Final Inspection | 5/27/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | A | PASS |
|
|
Fire alarm finaled
|
FIR03-00214
| INSP-Final Inspection | 5/27/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | P | FAIL |
|
|
No actual inspections were done. At the start of the fire sprinkler inspection I found that a different backflow preventor has been installed. Verification of friction loss is needed. Need NFPA 25. Provide verification that exposed cpvc sprinkler piping in the riser room is ok. Also per inspector 409 the fire sprinkler plans need to be resubmitted which has not been done yet according to the history available on the computer. Fire alarm plans need to be resubmitted due to changes in zones and notification circuitry.
|
FIR04-00162
| INSP-Final Inspection | 5/27/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | P | FAIL |
|
|
No actual inspections were done. At the start of the fire sprinkler inspection I found that a different backflow preventor has been installed. Verification of friction loss is needed. Need NFPA 25. Provide verification that exposed cpvc sprinkler piping in the riser room is ok. Also per inspector 409 the fire sprinkler plans need to be resubmitted which has not been done yet according to the history available on the computer. Fire alarm plans need to be resubmitted due to changes in zones and notification circuitry.
|
MIS04-00133
| FIR-Final | 5/26/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | P | PASS |
|
|
fire life safety finaled 5/27/2004 3:06:33 PM
|
BLD02-01157
| FIRE-Final Inspection | 5/26/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | P | FAIL |
|
|
No actual inspections were done. At the start of the fire sprinkler inspection I found that a different backflow preventor has been installed. Verification of friction loss is needed. Need NFPA 25. Provide verification that exposed cpvc sprinkler piping in the riser room is ok. Also per inspector 409 the fire sprinkler plans need to be resubmitted which has not been done yet according to the history available on the computer. Fire alarm plans need to be resubmitted due to changes in zones and notification circuitry. 5/27/2004 3:34:05 PM
|
MIS04-00119
| FIR-Final | 5/27/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | P | PASS |
|
|
fire life safety finaled 5/27/2004 12:32:06 PM
|
BLD03-02057
| FIRE-Conference | 5/26/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | P | DONE |
|
|
pat; Phone #: ###-#### I spoke with pat about the exhuast duct and fire/smoke damper from the elevator equipment room to the exterior wall. He wants to have it exhaust to the roof. I spoke with the plan reviewer who said if they want to change things the contractor will need to resubmit 5/27/2004 11:56:08 AM
|
BLD04-00567
| FIRE-Final Inspection | 5/26/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 5/27/2004 12:33:17 PM
|
BLD04-00568
| FIRE-Final Inspection | 5/26/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 5/27/2004 12:33:27 PM
|
BLD04-00569
| FIRE-Final Inspection | 5/26/2004 | 5/27/2004 | 5/27/2004 12:00:00 AM | P | PASS |
|
|
fire life safety finaled 5/27/2004 12:33:37 PM
|