Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-00820 FIRE-Final Inspection5/26/20045/27/20045/27/2004 12:00:00 AMAPART
A temporary occupancy was given with dave millers permission until the fire alarm plans have been approved and work completed for the duct smoke detector addition. The unit in question is rated for 4000 cfm. 5/27/2004 8:25:51 AM
BLD04-00820 FIRE-Final Inspection5/26/20045/27/20045/27/2004 12:00:00 AMAPART
A temporary occupancy was given with dave millers permission until the fire alarm plans have been approved and work completed for the duct smoke detector addition. The unit in question is rated for 4000 cfm. 5/27/2004 8:25:51 AM
FIR04-00318 INSP-Sprinkler Rough-in/Hydro5/26/20045/27/20045/27/2004 12:00:00 AMAPASS
fire life safety finaled 5/27/2004 9:00:27 AM
BLD04-00151 FIRE-Final Inspection5/26/20045/27/20045/27/2004 12:00:00 AMAPASS
Fire life safety finaled 5/27/2004 10:40:34 AM
BLD04-00372 FIRE-Final Inspection5/26/20045/27/20045/27/2004 12:00:00 AMAFAIL
Provide approved door hardware on all doors in remodeled area. Relocate fire extinguisher to the T.I. space. Repair the existing exit sign. The two hvac units require duct smoke detectors for automatic shutdown. See review note #18. 5/27/2004 10:25:42 AM
FIR04-00318 INSP-Final Inspection5/27/20045/27/20045/27/2004 12:00:00 AMAPASS
fire sprinkler finaled
FIR04-00163 INSP-Final Inspection5/27/20045/27/20045/27/2004 12:00:00 AMAPASS
fire sprinklers finaled
FIR04-00101 INSP-Final Inspection5/27/20045/27/20045/27/2004 12:00:00 AMAPASS
Fire alarm finaled
FIR03-00214 INSP-Final Inspection5/27/20045/27/20045/27/2004 12:00:00 AMPFAIL
No actual inspections were done. At the start of the fire sprinkler inspection I found that a different backflow preventor has been installed. Verification of friction loss is needed. Need NFPA 25. Provide verification that exposed cpvc sprinkler piping in the riser room is ok. Also per inspector 409 the fire sprinkler plans need to be resubmitted which has not been done yet according to the history available on the computer. Fire alarm plans need to be resubmitted due to changes in zones and notification circuitry.
FIR04-00162 INSP-Final Inspection5/27/20045/27/20045/27/2004 12:00:00 AMPFAIL
No actual inspections were done. At the start of the fire sprinkler inspection I found that a different backflow preventor has been installed. Verification of friction loss is needed. Need NFPA 25. Provide verification that exposed cpvc sprinkler piping in the riser room is ok. Also per inspector 409 the fire sprinkler plans need to be resubmitted which has not been done yet according to the history available on the computer. Fire alarm plans need to be resubmitted due to changes in zones and notification circuitry.
MIS04-00133 FIR-Final5/26/20045/27/20045/27/2004 12:00:00 AMPPASS
fire life safety finaled 5/27/2004 3:06:33 PM
BLD02-01157 FIRE-Final Inspection5/26/20045/27/20045/27/2004 12:00:00 AMPFAIL
No actual inspections were done. At the start of the fire sprinkler inspection I found that a different backflow preventor has been installed. Verification of friction loss is needed. Need NFPA 25. Provide verification that exposed cpvc sprinkler piping in the riser room is ok. Also per inspector 409 the fire sprinkler plans need to be resubmitted which has not been done yet according to the history available on the computer. Fire alarm plans need to be resubmitted due to changes in zones and notification circuitry. 5/27/2004 3:34:05 PM
MIS04-00119 FIR-Final5/27/20045/27/20045/27/2004 12:00:00 AMPPASS
fire life safety finaled 5/27/2004 12:32:06 PM
BLD03-02057 FIRE-Conference5/26/20045/27/20045/27/2004 12:00:00 AMPDONE
pat; Phone #: ###-#### I spoke with pat about the exhuast duct and fire/smoke damper from the elevator equipment room to the exterior wall. He wants to have it exhaust to the roof. I spoke with the plan reviewer who said if they want to change things the contractor will need to resubmit 5/27/2004 11:56:08 AM
BLD04-00567 FIRE-Final Inspection5/26/20045/27/20045/27/2004 12:00:00 AMPPASS
Fire life safety finaled 5/27/2004 12:33:17 PM
BLD04-00568 FIRE-Final Inspection5/26/20045/27/20045/27/2004 12:00:00 AMPPASS
Fire life safety finaled 5/27/2004 12:33:27 PM
BLD04-00569 FIRE-Final Inspection5/26/20045/27/20045/27/2004 12:00:00 AMPPASS
fire life safety finaled 5/27/2004 12:33:37 PM