Inspections for the day of: Tuesday, May 27, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03879 ELE-Aging Inspection5/27/20085/27/20085/27/2008 4:02:50 PM FAIL
work has stopped for more than 1 year on this job
ELE06-03879 DOC - Permit Expired5/27/20085/27/20085/27/2008 4:01:52 PMPPASS
work has stopped for more than 1 year on this job
ELE07-04181 Electrical Rough-In5/27/20085/27/20085/27/2008 3:39:58 PMPPART
richard Note: trench Phone #: ###-####
underground ok
ELE08-00795 Final5/27/20085/27/20085/27/2008 2:35:19 PMPPASS
Call Joe if needed for Final. Emailed info containg requested info on poke thru floor boxes to PAT. Pat said Ok for final by email to me. The building engineer phone is ###-#### if needed,Sam is at this number. Phone #: ###-#### Internet Inspection Request from: Loren Ramsey
ELE08-01294 Permanent Service5/27/20085/27/20085/27/2008 2:07:12 PMPPASS
mark Phone #: ###-####
service has main and ground rods check water electrode and bonding on final
P/S O/H r Ok
ESC07-00510 Site Preparation5/27/20085/27/20085/27/2008 1:40:07 PMPFAIL
RP is no longer under contract for this job as it was taken over by the homeowner I gave them until tomorrow to become compliant.
ELE08-00762 Permanent Service5/27/20085/27/20085/27/2008 12:44:16 PMPFAIL
Transformer inspection Phone #: ###-#### Internet Inspection Request from: Celinda Winters
transformer not connected properly or corner grounded also requires circuit breakers instead of fuses.
ESC06-00853 Site Preparation5/27/20085/27/20085/27/2008 12:11:34 PMPPASS
sign posted
ELE08-01308 Rough-In Permanent Service5/22/20085/27/20085/27/2008 12:08:13 PMACANC
rescheduled to today as per Pat Lass''s request on 5/22/08. Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
Jim talked to Dan
ELE07-00134 Electrical Rough-In5/23/20085/27/20085/27/2008 10:01:05 AMAPART
Rene Phone #: ###-####
ceiling anop
ELE07-03279 Final5/23/20085/27/20085/27/2008 9:39:08 AMAPASS
Rene Phone #: ###-####
ELE06-02124 Conference5/23/20085/27/20085/27/2008 9:04:43 AMAPART
naomi - please call 1/2 hr prior to inspection Phone #: ###-####
talked about ground wires make-up, nail plates and 6 in free conductor and required receps.