Inspections for the day of: Tuesday, May 27, 2008.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-02935 FIRE-Final Inspection5/27/20085/27/20085/27/2008 4:41:42 PMPPASS
Retested non-functional HVAC unit duct detector for verification of repair, two EM lights at the kitchen and service area okayed, final fire life safety inspection passed.
FIR07-00967 INSP-Final Inspection5/23/20085/27/20085/27/2008 4:16:25 PMADEFR
Scheduled by a contractor via Hello! on 5/23/2008 at 4:19:56 PM. Contact: ###-####.
FIR07-00905 INSP-Sprinkler Rough-in/Hydro5/27/20085/27/20085/27/2008 3:48:48 PMPPART
UG fire supply line hydrostatic testing for the new portion of installed pipe and ductile riser completed acceptable.
FIR07-00702 INSP-Sprinkler Rough-in5/23/20085/27/20085/27/2008 3:46:57 PMAFAIL
Inspection for cover failed at four locations-see plan set for annotations including missing coverage at one storage room, blocked pendent at a patient room by an adjacent curtain track, one overspaced hanger at the corridor, one head to be relocated due to blockage by a cabinet, mc cable is not to be attatched to sprinkler hanger rods-removed while on site, remainder of ceilings are okay for cover as initialed with today's date.
FIR07-00812 INSP-Sprinkler Rough-in/Hydro5/23/20085/27/20085/27/2008 2:05:50 PMPFAIL
Rough-in cover inspection for the office area failed due to decking insulation covering all pipe hanger attatchments-need to expose the work for verification of seismic restraint at the beam clamps-selected one random hanger for inspection and discovered the retaining strap had not been fastened, also missing EQ bracing at the 3" main, noted stairway heads are not cut, need to provide approved plan set.
FIR08-00337 INSP-Final Inspection5/23/20085/27/20085/27/2008 1:07:24 PMACANC
rick - please call 1/2 hr prior to inspection Phone #: ###-#### Overbooked
FIR08-00347 INSP-Final Inspection5/27/20085/27/20085/27/2008 1:07:01 PMPCANC
javaer Phone #: ###-#### Overbooked
FIR08-00352 INSP-Final Inspection5/23/20085/27/20085/27/2008 1:06:43 PMACANC
javaer Phone #: ###-#### Overbooked
MIS08-00086 FIR-Conference5/23/20085/27/20085/27/2008 12:11:01 PMADONE
No fire inspection related signatures are required for this project per conversation with J. Sly structural inspector.
FIR07-00902 INSP-Sprinkler Rough-in5/27/20085/27/20085/27/2008 12:08:46 PMPFAIL
Pendent head at the mechanical room 2nd floor is obstructed by an adjacent duct-need to relocate as discussed, remainder of hard lid ceilings are good for cover.
FIR08-00303 INSP-Sprinkler Rough-in5/23/20085/27/20085/27/2008 12:06:50 PMAPART
See stamped TI plan set for rough-in areas approved for cover at the hard lid ceilings including soffits, noted head placement to be adjusted at the conference room accordian door pocket for proper coverage, ceiling at the electrical closet appears to have been deleted-if so then walls must extend to the bottom of the deck for area separation of sprinklered and non-sprinklered spaces.
FIR08-00204 INSP-Sprinkler Rough-in/Hydro5/22/20085/27/20085/27/2008 11:31:14 AMPCANC
ken - underground and tenting for cover Phone #: ###-#### Overbooked
FIR08-00039 INSP-Final Inspection5/27/20085/27/20085/27/2008 11:24:10 AMPNR
Permit work is not yet completed for final approval, system riser #2 feeding the east remodel is not in service as rough-in is not finished, riser #1 supervisory and alarm system interconnection tested okay-fire sprinkler install for work completed to date for "phase 1" appears acceptable.
BLD08-00359 FIRE-Final Inspection5/27/20085/27/20085/27/2008 11:19:27 AMPCANC
juseppe Phone #: ###-#### Overbooked
FIR08-00114 FIR-Aging Inspection5/27/20085/27/20085/27/2008 11:10:53 AM DONE
In progress, pending site inspection request.
BLD08-01079 FIRE-Final Inspection5/22/20085/27/20085/27/2008 11:09:26 AMACANC
Don Phone #: ###-#### Overbooked
BLD08-00315 FIRE-Final Inspection5/23/20085/27/20085/27/2008 11:05:10 AMACANC
jeff Phone #: ###-#### Overbooked
FIR08-00168 INSP-Final Inspection5/23/20085/27/20085/27/2008 11:04:43 AMAFAIL
Provide as-built plans indicating field change in notification circut wire guage from 14 to 18, the deletion of a duct smoke detector at the electrical room and the additon of a requried notification appliance at the basement storage room per review notes, provide an updated map at the panel, the door to the FACP room needs signage, sprinkler system riser #2 is not in service to complete testing, annotated areas not finished at this time including phase 2 appliance circut, central station account information is not correct regarding type and description of signals recieved-will need to retest.
BLD06-00014 FIRE-Final Inspection5/23/20085/27/20085/27/2008 12:00:00 AMPCANC
russ - fire life safety Phone #: ###-####