Inspections for the day of: Wednesday, May 27, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00727 FIRE-Final Inspection5/27/20095/27/20095/27/2009 3:59:20 PMPPASS
life safety passed.
FIR09-00133 INSP-Final Inspection5/26/20095/27/20095/27/2009 3:29:25 PMAFAIL
As per my discussion with Tim Frost and Greg Patrick the dry system needs to have the air maintenance device installed as per approved drawing note 15 and 18. The air compressor exceeded the 30 pump up time but Jeremy was going to drop the air pressure down 2 or 3 pounds so that the 30 minute limitation is met. All other items including the fire alarm interconnection is complete.
FIR09-00325 INSP-Final Inspection5/27/20095/27/20095/27/2009 3:26:58 PMPFAIL
This project can not be finaled because per the scope of work this project has two phases. Only phase one has been completed. Also the 1 1/2" grooved cply closest to the wall is leaking as is the pipe o let. Also the orange shipping clip is still attached to the new pendant in the restroom.
FIR09-00089 INSP-Final Inspection5/21/20095/27/20095/27/2009 2:30:09 PMAPASS
Permit finaled.
FIR09-00086 INSP-Final Inspection5/21/20095/27/20095/27/2009 2:29:41 PMAFAIL
All signals were sent out the problem is the lower gate valve tamper switch needs adjusted. I could disable the sprinkler system by shutting the valve and the panel did not recognize the valve as being shut.
FIR09-00092 INSP-Final Inspection5/21/20095/27/20095/27/2009 1:42:29 PMAFAIL
We had access to the building but no access to the fire alarm panel. No testing was performed.
FIR09-00168 INSP-Final Inspection5/26/20095/27/20095/27/2009 1:26:20 PMAPASS
Permit finaled. The originally submitted AES panel has installed now.
FIR08-00832 INSP-Sprinkler Rough-in/Hydro5/26/20095/27/20095/27/2009 10:01:50 AMAPASS
The first floor of Building C sprinkler piping can be covered with sheet rock. The insulation has been installed.
FIR09-00276 INSP-Final Inspection5/26/20095/27/20095/27/2009 10:01:01 AMAPASS
Permit finaled
FIR09-00107 FIR-Aging Inspection5/27/20095/27/20095/27/2009 6:23:50 AM NR
work is in progress