Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00236 ELE-Aging Inspection5/27/20115/27/20115/31/2011 9:47:58 AM DONE
wsuc
ELE11-00287 Electrical Rough-In5/27/20115/27/20115/27/2011 2:08:55 PMPPART
inspection done on different permit #
ELE11-00971 Permanent Service5/23/20115/27/20115/27/2011 2:03:20 PMAPASS
Phone #: ###-#### >> Inspection requested via web by shane miller
p/s u/g rec. ok
ELE11-00330 Permanent Service5/26/20115/27/20115/27/2011 12:09:37 PMAPASS
Mike Phone #: ###-#### p/s o/h new ok
ELE11-00711 Final5/26/20115/27/20115/27/2011 12:09:13 PMAPASS
Phone #: ###-#### >> Inspection requested via web by Clint Tate card signed
ELE11-00793 Final5/26/20115/27/20115/27/2011 12:08:52 PMAPASS
Mike Phone #: ###-#### >> Inspection requested via web by Sean DeLacy ok card signed
ELE11-00954 Final5/26/20115/27/20115/27/2011 12:08:25 PMAPASS
Nick Phone #: ###-#### card signed
ELE11-00432 Permanent Service5/27/20115/27/20115/27/2011 12:08:02 PMPPASS
Cory Phone #: p/s o/h new ok
GCE11-00056 GCE-Rough-In Permanent Service5/26/20115/27/20115/27/2011 8:37:14 AMAFAIL
Rough-In/Perm ServiceDale @ ###-#### or ###-####Call in advance talked with owner, correction posted 250.24(A)(1) shall terminate GEC at neutral bus, needs to install green bond screw312.5(C) romex and water bond shall enter p/s panel with a connector note owner needs to post address at site