Inspections for the day of: Friday, May 27, 2011.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00064 INSP-Final Inspection5/27/20115/27/20115/27/2011 3:07:09 PMPFAIL
Need updated map at the facp showing the correct duct smoke detector addresses and the new pull station at the west exit door. Also the duct detector addresses tested do not correspond with the addresses received at central. To final a map and reverification of duct detector addresses will be required.
FIR11-00130 INSP-Supply line flush5/26/20115/27/20115/27/2011 2:55:35 PMPFAIL
I waited 45 minutes for United Water to show up for an underground flush. They never arrived so no flush was performed.
BLD11-00140 FIRE-Final Inspection5/26/20115/27/20115/27/2011 2:45:51 PMPPASS
Life safety passed. Door indicators to be covered by the building inspector.
FIR11-00215 INSP-Final Inspection5/26/20115/27/20115/27/2011 2:05:44 PMACANC
To be canceled per phone conversation with Mary. Also per phone conversation with Jerry McAdams with the Boise Fire Dept. the manual pull station is required to meet current code requirements for spacing from the hood. It is currently located less than 10' from the hood. No actual inspection has been performed at this project.
BLD11-00437 FIRE-Final Inspection5/26/20115/27/20115/27/2011 9:24:57 AMAPASS
life safety passed
FIR11-00064 INSP-Final Inspection5/26/20115/27/20115/27/2011 9:13:23 AMAPART
Four strobes are over spaced. One strobe needs to be lowered since it is obstructed by duct work. The central station did not receive all of the alarm signals. The inspection had to be stopped due to time constraints. The remaining inspection is scheduled for later today.
FIR11-00149 INSP-Final Inspection5/26/20115/27/20115/27/2011 12:00:00 AMAPASS
Inspection passed.




Troy call me when you get an idea of a time ###-#### so I can meet you onsite. Thx Jason Phone #: ###-#### >> Inspection requested via web by Jason Gale