FIR11-00064
| INSP-Final Inspection | 5/27/2011 | 5/27/2011 | 5/27/2011 3:07:09 PM | P | FAIL |
|
|
Need updated map at the facp showing the correct duct smoke detector addresses and the new pull station at the west exit door. Also the duct detector addresses tested do not correspond with the addresses received at central. To final a map and reverification of duct detector addresses will be required.
|
FIR11-00130
| INSP-Supply line flush | 5/26/2011 | 5/27/2011 | 5/27/2011 2:55:35 PM | P | FAIL |
|
|
I waited 45 minutes for United Water to show up for an underground flush. They never arrived so no flush was performed.
|
BLD11-00140
| FIRE-Final Inspection | 5/26/2011 | 5/27/2011 | 5/27/2011 2:45:51 PM | P | PASS |
|
|
Life safety passed. Door indicators to be covered by the building inspector.
|
FIR11-00215
| INSP-Final Inspection | 5/26/2011 | 5/27/2011 | 5/27/2011 2:05:44 PM | A | CANC |
|
|
To be canceled per phone conversation with Mary. Also per phone conversation with Jerry McAdams with the Boise Fire Dept. the manual pull station is required to meet current code requirements for spacing from the hood. It is currently located less than 10' from the hood. No actual inspection has been performed at this project.
|
BLD11-00437
| FIRE-Final Inspection | 5/26/2011 | 5/27/2011 | 5/27/2011 9:24:57 AM | A | PASS |
|
|
life safety passed
|
FIR11-00064
| INSP-Final Inspection | 5/26/2011 | 5/27/2011 | 5/27/2011 9:13:23 AM | A | PART |
|
|
Four strobes are over spaced. One strobe needs to be lowered since it is obstructed by duct work. The central station did not receive all of the alarm signals. The inspection had to be stopped due to time constraints. The remaining inspection is scheduled for later today.
|
FIR11-00149
| INSP-Final Inspection | 5/26/2011 | 5/27/2011 | 5/27/2011 12:00:00 AM | A | PASS |
|
|
Inspection passed.
Troy call me when you get an idea of a time ###-#### so I can meet you onsite. Thx Jason Phone #: ###-#### >> Inspection requested via web by Jason Gale
|