FIR14-00076
| INSP-Sprinkler Rough-in/Hydro | 5/27/2014 | 5/27/2014 | 5/27/2014 3:31:29 PM | P | PASS |
|
|
Overhead hydro test of the 4" wet system passed
|
FIR14-00276
| INSP-Sprinkler Rough-in/Hydro | 5/23/2014 | 5/27/2014 | 5/27/2014 3:30:54 PM | A | PASS |
|
|
See the city approved plans for piping above hardlids that is ok to cover.
|
FIR14-00155
| INSP-Final Inspection | 5/23/2014 | 5/27/2014 | 5/27/2014 2:53:58 PM | P | PASS |
|
|
Permit finaled
|
BLD14-00321
| FIRE-Final Inspection | 5/23/2014 | 5/27/2014 | 5/27/2014 2:53:14 PM | P | FAIL |
|
|
Project was not ready for a final yet. Scott Arellano and I discussed the two gates on the west side of the bulding and scott ultimately approved their location and width. Fire sprinkler permit is complete. Per Carl Westfall no locking mechanisam can impede exiting so a delay locks can not be installed. They can only sound an alarm upon unauthorized access.
|
BLD14-01251
| FIRE-Final Inspection | 5/12/2014 | 5/27/2014 | 5/27/2014 10:23:18 AM | A | PASS |
|
|
life safety passed
|
BLD14-01197
| FIRE-Final Inspection | 5/23/2014 | 5/27/2014 | 5/27/2014 9:57:58 AM | A | FAIL |
|
|
Provide stickers at the main exit doors, remove dead bolts and provide single action hardware on the other two exterior exit doors. Provide missing exit sign. Resubmit plans showing the vestibule being deleted and a fenced enclosure being added.
|
FIR14-00155
| INSP-Sprinkler Rough-in/Hydro | 5/23/2014 | 5/27/2014 | 5/23/2014 10:58:15 AM | P | CANC |
|
|
Final Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|