Inspections for the day of: Wednesday, May 27, 2015.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00015 INSP-Sprinkler Rough-in/Hydro5/27/20155/27/20155/27/2015 3:33:06 PMPPASS
rough-in passed
FIR14-00756 INSP-Sprinkler Rough-in/Hydro5/26/20155/27/20155/27/2015 2:59:16 PMPPASS
Rough-in and tenting inspection passed. Piping can be covered.
FIR14-00757 INSP-Sprinkler Rough-in/Hydro5/26/20155/27/20155/27/2015 2:43:38 PMPPASS
Rough-in and tenting inspeciton passed. Piping can be covered.
FIR15-00064 INSP-Alarm Testing5/26/20155/27/20155/27/2015 2:38:30 PMPDONE
Todays inspection we verified the Faast detection system (problems with low air and water flow), and verified the devices in the Warehouse. I noted that door mags are being used for security and will need to be addressed with the appropriate Fire Code and NFPA requirements.
BLD15-00953 FIRE-Final Inspection5/27/20155/27/20155/27/2015 2:33:04 PMPPASS
Life safety passed
FIR15-00064 INSP-Final Inspection5/22/20155/27/20155/27/2015 2:32:07 PMACANC
Duplicate inspection
FIR15-00316 INSP-Alarm Testing5/26/20155/27/20155/27/2015 2:30:57 PMPFAIL
The low air signal needs to be a "supervisory" signal, not an alarm signal. The "waterflow" pressure switch on the pre-action system did not activate upon the trip of the system.
BLD15-01716 FIRE-Final Inspection5/27/20155/27/20155/27/2015 1:25:15 PMPPASS
Life safety passed
FIR15-00281 INSP-Supply line flush5/26/20155/27/20155/27/2015 10:26:42 AMAPASS
Supply line flush passed
FIR15-00280 INSP-Supply line flush5/26/20155/27/20155/27/2015 10:25:47 AMAPASS
Supply line flush passed.
FIR15-00278 INSP-Supply line flush5/26/20155/27/20155/27/2015 10:24:24 AMAPASS
Supply line flush passed
FIR15-00276 INSP-Supply line flush5/26/20155/27/20155/27/2015 10:22:31 AMAPASS
Supply line flush passed
FIR15-00279 INSP-Supply line flush5/26/20155/27/20155/27/2015 10:18:24 AMAPASS
Supply piping flush passed
FIR15-00277 INSP-Supply line flush5/26/20155/27/20155/27/2015 10:17:20 AMAPASS
Supply piping flush passed
FIR15-00278 INSP-Supply line flush5/26/20155/27/20155/27/2015 9:57:47 AMAPASS
Supply line flush passed
FIR15-00278 INSP-Supply line flush5/26/20155/27/20155/27/2015 9:56:44 AMAPASS
Supply line flush passed