FIR15-00015
| INSP-Sprinkler Rough-in/Hydro | 5/27/2015 | 5/27/2015 | 5/27/2015 3:33:06 PM | P | PASS |
|
|
rough-in passed
|
FIR14-00756
| INSP-Sprinkler Rough-in/Hydro | 5/26/2015 | 5/27/2015 | 5/27/2015 2:59:16 PM | P | PASS |
|
|
Rough-in and tenting inspection passed. Piping can be covered.
|
FIR14-00757
| INSP-Sprinkler Rough-in/Hydro | 5/26/2015 | 5/27/2015 | 5/27/2015 2:43:38 PM | P | PASS |
|
|
Rough-in and tenting inspeciton passed. Piping can be covered.
|
FIR15-00064
| INSP-Alarm Testing | 5/26/2015 | 5/27/2015 | 5/27/2015 2:38:30 PM | P | DONE |
|
|
Todays inspection we verified the Faast detection system (problems with low air and water flow), and verified the devices in the Warehouse. I noted that door mags are being used for security and will need to be addressed with the appropriate Fire Code and NFPA requirements.
|
BLD15-00953
| FIRE-Final Inspection | 5/27/2015 | 5/27/2015 | 5/27/2015 2:33:04 PM | P | PASS |
|
|
Life safety passed
|
FIR15-00064
| INSP-Final Inspection | 5/22/2015 | 5/27/2015 | 5/27/2015 2:32:07 PM | A | CANC |
|
|
Duplicate inspection
|
FIR15-00316
| INSP-Alarm Testing | 5/26/2015 | 5/27/2015 | 5/27/2015 2:30:57 PM | P | FAIL |
|
|
The low air signal needs to be a "supervisory" signal, not an alarm signal. The "waterflow" pressure switch on the pre-action system did not activate upon the trip of the system.
|
BLD15-01716
| FIRE-Final Inspection | 5/27/2015 | 5/27/2015 | 5/27/2015 1:25:15 PM | P | PASS |
|
|
Life safety passed
|
FIR15-00281
| INSP-Supply line flush | 5/26/2015 | 5/27/2015 | 5/27/2015 10:26:42 AM | A | PASS |
|
|
Supply line flush passed
|
FIR15-00280
| INSP-Supply line flush | 5/26/2015 | 5/27/2015 | 5/27/2015 10:25:47 AM | A | PASS |
|
|
Supply line flush passed.
|
FIR15-00278
| INSP-Supply line flush | 5/26/2015 | 5/27/2015 | 5/27/2015 10:24:24 AM | A | PASS |
|
|
Supply line flush passed
|
FIR15-00276
| INSP-Supply line flush | 5/26/2015 | 5/27/2015 | 5/27/2015 10:22:31 AM | A | PASS |
|
|
Supply line flush passed
|
FIR15-00279
| INSP-Supply line flush | 5/26/2015 | 5/27/2015 | 5/27/2015 10:18:24 AM | A | PASS |
|
|
Supply piping flush passed
|
FIR15-00277
| INSP-Supply line flush | 5/26/2015 | 5/27/2015 | 5/27/2015 10:17:20 AM | A | PASS |
|
|
Supply piping flush passed
|
FIR15-00278
| INSP-Supply line flush | 5/26/2015 | 5/27/2015 | 5/27/2015 9:57:47 AM | A | PASS |
|
|
Supply line flush passed
|
FIR15-00278
| INSP-Supply line flush | 5/26/2015 | 5/27/2015 | 5/27/2015 9:56:44 AM | A | PASS |
|
|
Supply line flush passed
|