Inspections for the day of: Friday, May 27, 2016.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-02740 Electrical Rough-In5/27/20165/27/20165/27/2016 3:09:23 PMPPASS
Zack Phone #: ###-####
1st floor exterior wall east 1/2 and conference room walls rough in ok cover
ELE16-01333 Final5/27/20165/27/20165/27/2016 2:25:04 PMPNH
Final for this project. Future for X-Ray machine. Contact is David Joseph ###-####. Please call if you have any questions as David will not be on site. Thank you and have a super weekend. Phone #: ###-#### Inspection requested via web by Laura Longshaw
Doors locked called left message
ELE16-00991 Final5/27/20165/27/20165/27/2016 2:05:01 PMPPASS
Corrections made. Final ok
ELE13-01291 Conference5/27/20165/27/20165/27/2016 12:22:59 PMADONE
requesting a consultation for JUMP site water feature bonding. Phone #: ###-#### Inspection requested via web by Brandon Robinson
Discussed bonding of area around fountain and foggers. Bonds required on rebar on each perimeter area to equipment and GFCI protection
ELE16-01697 Conference5/26/20165/27/20165/27/2016 11:15:35 AMADONE
Please call me when you are on your way, I will meet you there. Thanks Phone #: ###-#### Inspection requested via web by Troy Cobb
Discussed changing service which is located on as out building if required to change feeders to house in anyway. House not being worked on or changed just feeders reconnected. OK to just refeed house with no additional disconnecting means for or at house do to inspected and passed when originally installed. Work on this permit to include service change and possible turning out building into an office.
ELE16-00991 Final5/26/20165/27/20165/27/2016 10:35:59 AMAFAIL
Call John Binfet for access ###-#### Phone #: ###-#### Inspection requested via web by jamie berg
210.8(B)- Receptcle outlet located within 6' of sink in old kitchen area shall have GFCI protection.
*Receptacle outlets in basement not working.
ELE16-00329 Final5/26/20165/27/20165/27/2016 10:02:00 AMAFAIL
###-#### 3rd or 4th floor prewalk final
Lighting not working in 1 large room on 3 and 1 on 4. All electrical rooms to be checked in future and will check lighting then.