Inspections for the day of: Friday, May 27, 2016.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02185 ELE-Aging Inspection5/27/20165/27/20165/31/2016 8:00:16 AM CANC
too busy
ELE12-03014 ELE-Aging Inspection5/27/20165/27/20165/31/2016 7:59:48 AM CANC
too busy
ELE16-01596 Electrical Rough-In5/27/20165/27/20165/27/2016 2:25:32 PMPFAIL
Dan Phone #: ###-####
334.12 Type NM cable shall be protected from physical damage(wires hanging and installed in front of sheetrock)
334.30 Type NM cable shall be secured within 12" of a box and every 4 1/2' there after
300.4(d) cables shall not be secured closer then 1 1/4 within edge of framing member
314.29 j-boxes shall be readily acessible
ELE16-00075 Final5/27/20165/27/20165/27/2016 1:45:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Shaun Kirkman
corrections as noted final ok
ELE15-03543 Final5/27/20165/27/20165/27/2016 12:42:29 PMPPASS
Phone #: ###-#### Inspection requested via web by Kotton Corder
Pool final ok
ELE16-00942 Final5/27/20165/27/20165/27/2016 12:12:16 PMPFAIL
Lockbox is 02468. I you have any questions, please call Clay ###-####. Thank You!! Phone #: ###-#### Inspection requested via web by Clay Morgan
356.42 only listed fittings shall be used for LFNC(furnace has not connector)
422.31 fixed appliances shall have a means of lockout
ELE16-01698 Electrical Rough-In5/26/20165/27/20165/27/2016 11:36:08 AMAPASS
Somebody is supposed to be there. Angeleah is the contact ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
Back ADA bath ok cover
ELE16-01358 Final5/26/20165/27/20165/27/2016 11:24:44 AMAPASS
Please call so I can meet you to let you in
###-####
Thanks
Eddy Phone #: ###-#### Inspection requested via web by Eddy Udry
Final for living room adittion ok
ELE16-01528 Final5/26/20165/27/20165/27/2016 10:23:38 AMAFAIL
Phone #: ###-#### Inspection requested via web by Matthew White
408.41 Grounded conductor shall terminate within a panelboard in a individual terminal
230.71 Maximun number of DIsc. shall not be greater then 6 without a main disc.
250 no bonding jumper and isolate grounding and grounded condutor
225.38 main disc means required for seperate structure and shall be held in place as per 408.36(d)
ELE16-00186 Final5/26/20165/27/20165/27/2016 9:47:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson
EC blank fixture box above bathtub. correcions fixed final ok
ELE16-01174 Electrical Rough-In5/26/20165/27/20165/27/2016 9:25:44 AMAPASS
Zahid Phone #: ###-####
Will need to verify main disc. means for seperate structure. Detached garage ok cover
ELE16-01427 Electrical Rough-In5/26/20165/27/20165/27/2016 9:08:16 AMAPASS
please call half hour prior to inspection Phone #: ###-#### Inspection requested via web by John Edwards
Prep-kitchen and storage area cielings only ok cover
ELE16-01427 Final5/27/20165/27/20165/27/2016 9:08:01 AMPPART
please call half hour prior to inspection Phone #: ###-#### Inspection requested via web by John Edwards
Prep-kitchen ok to occupy
ELE16-01561 Rough-In Permanent Service5/26/20165/27/20165/27/2016 8:43:10 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
rough-in ok cover p/s u/g n ok
ELE16-01283 Final5/26/20165/27/20165/26/2016 3:23:46 PMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn correction fixed final ok