Inspections for the day of: Friday, May 27, 2016.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00909 INSP-Sprinkler Rough-in5/26/20165/27/20165/27/2016 2:17:09 PMAPASS
An additional lenght of piping is ok for cover. Tie-in to the Suez tap is taking place.
BLD16-01719 FIRE-Final Inspection5/27/20165/27/20165/27/2016 2:14:02 PMPFAIL
Provide separate permit from the Boise Fire Dept. as per review note #1, install and provide testing of the "Emergency Off" switch per note #2, Provide signage per review note #3, Provide fire extingusher per review note #4 and approved plans, Provide vehicle impact protection per review note #5 (see IFC 312 #2, #3, #4), provide signage per IFC 5003.5

Shawn Phone #: ###-####
FIR16-00303 INSP-Final Inspection5/27/20165/27/20165/27/2016 1:34:48 PMPPASS
Permit finaled
FIR16-00335 INSP-Supply line flush5/26/20165/27/20165/27/2016 1:31:46 PMAPASS
Underground supply line hydro tests passed
FIR16-00348 INSP-Sprinkler Rough-in5/27/20165/27/20165/27/2016 1:12:51 PMPPASS
rough-in passed. piping can be covered.
BLD16-00591 FIRE-Final Inspection5/27/20165/27/20165/27/2016 1:09:53 PMPFAIL
See the city approved plans for corrections noted that include removing the manual flush bolts from the inactive leaf of the main exit door and providing automatic flush bolts, removing the keyed deadbolt from the existing office exterior exit door, providing an exit light and emergency lighting above the exxterior exit door, and removing the two thumbturn deadbolts from the interior office doors. I discussed with the general contractor that the round knobs on the interior door may need to be replaced at the building inspector discression
BLD16-00427 FIRE-Final Inspection5/26/20165/27/20165/27/2016 11:10:00 AMPPASS
life safety passed
BLD16-01451 FIRE-Final Inspection5/26/20165/27/20165/27/2016 10:58:53 AMAPASS
Life safety passed
FIR16-00355 INSP-Final Inspection5/26/20165/27/20165/27/2016 10:56:34 AMAPASS
Hood suppression system functioned correctly. Manual pull station position approved by the fire dept.
BLD16-00268 FIRE-Final Inspection5/27/20165/27/20165/27/2016 9:48:51 AMPPART
Life safety for phase 1 passed
BLD16-00268 FIRE-Alarm Testing5/27/20165/27/20165/27/2016 9:25:55 AMAPART
Phase 1 life safety passed.
NAF16-00013 INSP-Final5/26/20165/27/20165/27/2016 8:44:19 AMAPASS
Permit finaled
NAF16-00042 INSP-Final5/26/20165/27/20165/27/2016 8:43:48 AMAPASS
Permit finaled
FIR16-00239 INSP-Sprinkler Rough-in5/26/20165/27/20165/27/2016 8:06:29 AMAPASS
Sprinkler work is complete in the COnference Room.
BLD16-00699 FIRE-Final Inspection5/26/20165/27/20165/27/2016 8:04:47 AMAPART
Life safety passed in Open Work Area 129 and 121 and the Conference Room.
BLD16-00170 FIRE-Final Inspection5/27/20165/27/20165/27/2016 12:00:00 AMPDONE