FIR02-00124
| INSP-Final Inspection | 5/24/2002 | 5/28/2002 | 5/28/2002 12:00:00 AM | A | FAIL |
|
|
SHAUN ###-#### need compatibility for smoke detector and Record of Completion 5/28/2002 10:19:13 AM
|
BLD02-00015
| FIRE-Final Inspection | 5/24/2002 | 5/28/2002 | 5/28/2002 12:00:00 AM | A | FAIL |
|
|
KEITH ###-#### PLEASE CALL FIRST SO KEITH CAN MEET YOU // they are phasing this project and it is okay to use the new lounge; panic hardware to be installed on between bathroom and weightroom; exit sign to have arrows blanked out; address for permit is wrong - should be 3304 Lake Harbor 5/28/2002 10:18:36 AM
|
BLD02-00197
| FIRE-Final Inspection | 5/28/2002 | 5/28/2002 | 5/28/2002 12:00:00 AM | P | FAIL |
|
|
###-#### dan need alarm plans submitted per plan review notes; strobes not covering all areas; detectors within 3 ft of supply diffusers in hallways; there appears to be 2 in duct detectors as there are two remote LED's; not HVAC plans 5/28/2002 2:55:15 PM
|
BLD01-03139
| FIRE-Final Inspection | 5/28/2002 | 5/28/2002 | 5/28/2002 12:00:00 AM | P | PASS |
|
|
###-#### dan
|
FIR02-00168
| INSP-Sprinkler Rough-in | 5/28/2002 | 5/28/2002 | 5/28/2002 12:00:00 AM | P | PART |
|
|
Added by Inspector: 409 On 5/28/2002 1:29:47 PM underground okay to cover, all thrust blocks in; need to flush and hydro
|
FIR02-00140
| INSP-Final Inspection | 5/28/2002 | 5/28/2002 | 5/28/2002 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 409 On 5/28/2002 2:47:07 PM
|
FIR02-00124
| INSP-Final Inspection | 5/28/2002 | 5/28/2002 | 5/28/2002 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 409 On 5/28/2002 4:00:19 PM received compatibility and record of completion
|