Inspections for the day of: Wednesday, May 28, 2008.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00830 INSP-Alarm Testing5/23/20085/28/20085/29/2008 1:45:43 PMAPART
See approved plans for areas inspected today, noted smoke detectors at six patient rooms to be relocated, construction is still underway at some locations.KR
FIR07-00086 INSP-Sprinkler Rough-in5/27/20085/28/20085/28/2008 5:23:54 PMAPART
Approved for ceiling cover at the rooms initialed and annotated on stamped plan set, see as-built drawings for accurate floorplan and head layout also initialed with today's date.
FIR07-00702 INSP-Final Inspection5/27/20085/28/20085/28/2008 5:21:18 PMAPART
Previous c/n items are finished, rough-in approved for cover as red lined on plans.
FIR08-00124 INSP-Final Inspection5/27/20085/28/20085/28/2008 5:19:38 PMPCANC
Scheduled by a contractor via Hello! on 5/27/2008 at 4:28:25 PM. Contact: ###-####. Overbooked
BLD07-02932 FIRE-Final Inspection5/27/20085/28/20085/28/2008 5:17:58 PMPNR
Scheduled by a contractor via Hello! on 5/27/2008 at 3:54:24 PM. Contact: ###-####.
FIR08-00180 INSP-Final Inspection5/27/20085/28/20085/28/2008 5:17:22 PMPCANC
rod Phone #: ###-#### Overbooked
FIR08-00067 INSP-Final Inspection5/27/20085/28/20085/28/2008 5:16:41 PMPFAIL
Alarm line isolation valves must be secured in the open position(all risers), riser #6 pressure switch does not reset when trim line water psi is relieved.
FIR07-00967 INSP-Final Inspection5/28/20085/28/20085/28/2008 5:12:48 PMPDONE
Duplicate inspection request
FIR07-00967 INSP-Final Inspection5/28/20085/28/20085/28/2008 5:11:55 PMPPASS
Fire alarm permit finaled.
FIR07-00967 INSP-Conference5/27/20085/28/20085/28/2008 5:01:12 PMPPASS
Fire alarm permit work passed field testing, contractor to provide a signed copy of the record of completion per agreement, permit finaled.
BLD08-00536 FIRE-Final Inspection5/28/20085/28/20085/28/2008 4:58:27 PMPNR
Need project related fire alarm and sprinkler permits finaled prior to building life safety final.
FIR08-00313 INSP-Final Inspection5/27/20085/28/20085/28/2008 4:44:55 PMAPASS
Defficiencies regarding voice evac repaired, fire alarm permit finaled.
BLD08-00517 FIRE-Final Inspection5/27/20085/28/20085/28/2008 4:43:15 PMAPASS
Scope of work completed okay with the exception of approved door hardware at the exam room-contractor to provide correct type prior to structural final inspection.
FIR08-00352 INSP-Final Inspection5/27/20085/28/20085/28/2008 4:39:13 PMAPASS
Rough-in installation and final inspections completed in conjunction, fire sprinkler permit finaled.
FIR08-00337 INSP-Final Inspection5/27/20085/28/20085/28/2008 4:37:38 PMAPASS
Fire alarm work passed field test-one a/v cd setting adjusted while on site, permit finaled.
FIR08-00347 INSP-Final Inspection5/27/20085/28/20085/28/2008 4:35:35 PMAFAIL
Work is not completed for final inspection at this time.
FIR08-00346 INSP-Sprinkler Rough-in/Hydro5/28/20085/28/20085/28/2008 4:34:27 PMAPART
Overhead rough-in is approved for cover, final pending ceiling tile and escutcheon installation.
BLD08-00359 FIRE-Final Inspection5/27/20085/28/20085/28/2008 3:58:31 PMAPASS
Life safety inspection passed, tenant to remove curtain at the second exit doorway as discussed prior to structural final approval.
FIR07-00222 INSP-Final Inspection5/27/20085/28/20085/28/2008 3:56:20 PMAPASS
Missing retainers attatched per contractor verification, fire sprinkler permit finaled.
FIR08-00119 FIR-Aging Inspection5/28/20085/28/20085/28/2008 3:52:27 PM DONE
Construction underway, work in progress.
FIR08-00240 INSP-Final Inspection5/27/20085/28/20085/28/2008 3:51:23 PMAPASS
Corrections verified for completion, fire sprinkler permit finaled.