Inspections for the day of: Wednesday, May 28, 2008.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00204 INSP-Sprinkler Rough-in/Hydro5/27/20085/28/20085/28/2008 4:52:15 PMPPASS
cover tenting & underground hydro passed
FIR07-00874 INSP-Sprinkler Rough-in/Hydro5/28/20085/28/20085/28/2008 4:50:22 PMPPASS
The overhead hydro test of the ALF dry system passed.
BLD08-00675 FIRE-Final Inspection5/27/20085/28/20085/28/2008 3:36:06 PMAFAIL
Provide approved plans, provide fire extinguisher as discussed and provide approved hardware on the two new doors as discussed.
FIR08-00335 INSP-Final Inspection5/27/20085/28/20085/28/2008 3:34:53 PMAFAIL
The project can not be finaled. The rough-in passed and the piping can be covered.
FIR08-00117 INSP-Final Inspection5/28/20085/28/20085/28/2008 3:23:12 PMPFAIL
Photo room removed per Forrest notes. Waterflow bell out side in front of building did not function. Will call in for re-test. KR
FIR08-00098 INSP-Alarm Testing5/28/20085/28/20085/28/2008 2:30:21 PMPFAIL
Fire alarm testing completed. Failed due to bad sprinkler flow switch.KR
FIR08-00201 INSP-Alarm Testing5/28/20085/28/20085/28/2008 2:29:09 PMPFAIL
Fire alarm testing completed.Failed due to bad flow switch.KR
BLD07-02677 FIRE-Final Inspection5/27/20085/28/20085/28/2008 2:27:15 PMAFAIL
Life safety completed . Can not final shell permit until sprinkler flow switch is repaired. KR
BLD08-00169 FIRE-Final Inspection5/27/20085/28/20085/28/2008 2:26:28 PMAFAIL
Life safety completed . Can not final until sprinkler flow switch is repaired. KR
FIR07-00949 INSP-Final Inspection5/27/20085/28/20085/28/2008 2:23:46 PMAFAIL
Fire sprinkler testing complete ecept for bad flow switch. Will call in for re-test. KR
BLD07-02352 FIRE-Final Inspection5/28/20085/28/20085/28/2008 2:22:55 PMPFAIL
The fire extinguishers had not been installed, no address was installed and no one was one site to test the duct smoke detectors. Basically no inspection was performed.
BLD07-02391 FIRE-Final Inspection5/28/20085/28/20085/28/2008 2:22:19 PMPFAIL
The fire extinguishers had not been installed, no address was installed and no one was one site to test the duct smoke detectors. Basically no inspection was performed.
FIR08-00098 INSP-Final Inspection5/28/20085/28/20085/28/2008 2:19:53 PMPFAIL
Fire alarm test completed except for bad flow swicth. Will call in for re test. KR
FIR08-00201 INSP-Final Inspection5/28/20085/28/20085/28/2008 2:17:36 PMPFAIL
Fire alarm testing complete except for bad flow switch. Will call in for re-test. KR
FIR08-00076 INSP-Final Inspection5/27/20085/28/20085/28/2008 11:50:03 AMAFAIL
Provide factory verification that the duct smoke detector at address 45 can be located as installed. All other items are complete.
BLD08-00315 FIRE-Final Inspection5/27/20085/28/20085/28/2008 10:29:44 AMAFAIL
The two exit signs have been repaired but I need verification that a sprinkler permit was applied for and received since the sprinkler deficiencies previously noted have been corrected.
BLD07-02123 FIRE-Final Inspection5/28/20085/28/20085/28/2008 12:00:00 AMPCANC
ben Note: fire wall Phone #: ###-####