FIR08-00204
| INSP-Sprinkler Rough-in/Hydro | 5/27/2008 | 5/28/2008 | 5/28/2008 4:52:15 PM | P | PASS |
|
|
cover tenting & underground hydro passed
|
FIR07-00874
| INSP-Sprinkler Rough-in/Hydro | 5/28/2008 | 5/28/2008 | 5/28/2008 4:50:22 PM | P | PASS |
|
|
The overhead hydro test of the ALF dry system passed.
|
BLD08-00675
| FIRE-Final Inspection | 5/27/2008 | 5/28/2008 | 5/28/2008 3:36:06 PM | A | FAIL |
|
|
Provide approved plans, provide fire extinguisher as discussed and provide approved hardware on the two new doors as discussed.
|
FIR08-00335
| INSP-Final Inspection | 5/27/2008 | 5/28/2008 | 5/28/2008 3:34:53 PM | A | FAIL |
|
|
The project can not be finaled. The rough-in passed and the piping can be covered.
|
FIR08-00117
| INSP-Final Inspection | 5/28/2008 | 5/28/2008 | 5/28/2008 3:23:12 PM | P | FAIL |
|
|
Photo room removed per Forrest notes. Waterflow bell out side in front of building did not function. Will call in for re-test. KR
|
FIR08-00098
| INSP-Alarm Testing | 5/28/2008 | 5/28/2008 | 5/28/2008 2:30:21 PM | P | FAIL |
|
|
Fire alarm testing completed. Failed due to bad sprinkler flow switch.KR
|
FIR08-00201
| INSP-Alarm Testing | 5/28/2008 | 5/28/2008 | 5/28/2008 2:29:09 PM | P | FAIL |
|
|
Fire alarm testing completed.Failed due to bad flow switch.KR
|
BLD07-02677
| FIRE-Final Inspection | 5/27/2008 | 5/28/2008 | 5/28/2008 2:27:15 PM | A | FAIL |
|
|
Life safety completed . Can not final shell permit until sprinkler flow switch is repaired. KR
|
BLD08-00169
| FIRE-Final Inspection | 5/27/2008 | 5/28/2008 | 5/28/2008 2:26:28 PM | A | FAIL |
|
|
Life safety completed . Can not final until sprinkler flow switch is repaired. KR
|
FIR07-00949
| INSP-Final Inspection | 5/27/2008 | 5/28/2008 | 5/28/2008 2:23:46 PM | A | FAIL |
|
|
Fire sprinkler testing complete ecept for bad flow switch. Will call in for re-test. KR
|
BLD07-02352
| FIRE-Final Inspection | 5/28/2008 | 5/28/2008 | 5/28/2008 2:22:55 PM | P | FAIL |
|
|
The fire extinguishers had not been installed, no address was installed and no one was one site to test the duct smoke detectors. Basically no inspection was performed.
|
BLD07-02391
| FIRE-Final Inspection | 5/28/2008 | 5/28/2008 | 5/28/2008 2:22:19 PM | P | FAIL |
|
|
The fire extinguishers had not been installed, no address was installed and no one was one site to test the duct smoke detectors. Basically no inspection was performed.
|
FIR08-00098
| INSP-Final Inspection | 5/28/2008 | 5/28/2008 | 5/28/2008 2:19:53 PM | P | FAIL |
|
|
Fire alarm test completed except for bad flow swicth. Will call in for re test. KR
|
FIR08-00201
| INSP-Final Inspection | 5/28/2008 | 5/28/2008 | 5/28/2008 2:17:36 PM | P | FAIL |
|
|
Fire alarm testing complete except for bad flow switch. Will call in for re-test. KR
|
FIR08-00076
| INSP-Final Inspection | 5/27/2008 | 5/28/2008 | 5/28/2008 11:50:03 AM | A | FAIL |
|
|
Provide factory verification that the duct smoke detector at address 45 can be located as installed. All other items are complete.
|
BLD08-00315
| FIRE-Final Inspection | 5/27/2008 | 5/28/2008 | 5/28/2008 10:29:44 AM | A | FAIL |
|
|
The two exit signs have been repaired but I need verification that a sprinkler permit was applied for and received since the sprinkler deficiencies previously noted have been corrected.
|
BLD07-02123
| FIRE-Final Inspection | 5/28/2008 | 5/28/2008 | 5/28/2008 12:00:00 AM | P | CANC |
|
|
ben Note: fire wall Phone #: ###-####
|