Inspections for the day of: Thursday, May 28, 2009.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00015 INSP-Final Inspection5/27/20095/28/20095/28/2009 4:48:50 PMAPASS
Remainder of fire alarm work passed functional testing, permit approved for final status.
FIR08-00840 INSP-Sprinkler Rough-in/Hydro5/27/20095/28/20095/28/2009 4:44:09 PMAPART
Overhead installation at unit 1703 is acceptable for cover including the 17th and 18th floor levels.
FIR08-00786 INSP-Alarm Testing5/26/20095/28/20095/28/2009 4:42:46 PMAPART
Fire alarm testing completed for the second floor media center areas and adjacent corridors areas F and G, need access to test devices in one locked storage room, one SD to be added at the circulation desk, noted deleted points including door holders, dampers, relocated nac panel and deleted sd to be included on as-built set. Non-functional damper at the electrical room 1st floor retested okay after repair.
FIR09-00189 INSP-Supply line flush5/27/20095/28/20095/28/2009 2:18:24 PMAPART
UG fire supply line flush witnessed acceptable.
BLD07-02419 FIRE-Alarm Testing5/27/20095/28/20095/28/2009 2:05:46 PMAPASS
Final fire life safety walkthrough completed satisfactory, C/N items are finished, project related fire alarm and sprinkler permits are finaled, mag lock interconnections tested per fire alarm final by K. Roule, inspection passed. NOTE: inspection type is BLD- fire final.
BLD05-01680 FIRE-Final Inspection5/28/20095/28/20095/28/2009 2:02:00 PMPPASS
Fire life safety final okayed when project related fire alarm permit is detatched from this building permit per agreement with S. Arellano and M. Senteno.
BLD08-02249 FIRE-Final Inspection5/27/20095/28/20095/28/2009 1:59:29 PMAPART
Corrections at unit 554 completed. However, the smoke alarm at the second floor bedroom east side is not functional- notified contractor that repair is to be done and smoke alarm retested at structural final inspection.
BLD08-02331 FIRE-Final Inspection5/27/20095/28/20095/28/2009 1:57:16 PMAFAIL
Project related fire sprinkler permit is still in the "ready to issue" status and must be issued, called for final and approved prior to building life safety final, also noted hardware at the second exit door is not correct.
BLD09-00110 FIRE-Final Inspection5/27/20095/28/20095/28/2009 1:55:28 PMAPASS
Fire life safety inspection passed per the scope of work.