Inspections for the day of: Friday, May 28, 2010.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00711 INSP-Alarm Testing5/28/20105/28/20105/28/2010 3:32:19 PMPDONE
Relocate the a/v in the dining area, provide an additional strobe in the lobby and provide an additional strobe in the courtyard corridor as discussed and then test. Still need to verify operation of the remaining smoke dampers. Need map for facp and signal report
BLD07-02624 FIRE-Final Inspection5/27/20105/28/20105/28/2010 3:15:08 PMAFAIL
Repair the two emergency lights and provide fire extinguishers with a current inspection tag.
BLD06-02047 FIRE-Final Inspection5/27/20105/28/20105/28/2010 3:14:29 PMAFAIL
Repair the two emergency lights and provide fire extinguishers with a current inspection tag.
FIR10-00082 FIR-Aging Inspection5/28/20105/28/20105/28/2010 3:13:25 PM NR
Work is in progress.
FIR10-00060 INSP-Alarm Testing5/27/20105/28/20105/28/2010 3:12:42 PMADONE
Phase I fire alarm is complete.
BLD09-00557 FIRE-Final Inspection5/27/20105/28/20105/28/2010 3:11:50 PMAFAIL
The only item for life safety that was inspected today were the exit signs and emergency lighting. One exit sign needs to be added as shown on the city approved plans. Herb is calling in for a re-inspection for Tuesday.
BLD10-00608 FIRE-Conference5/27/20105/28/20105/28/2010 3:07:51 PMACANC
Rescheduled for monday
FIR10-00026 INSP-Final Inspection5/27/20105/28/20105/28/2010 3:06:22 PMAFAIL
Kenny Phone #: ###-####. Everything tested ok including the fire alarm interconnect. When Kenny provides the inspection and testing form this permit can be finaled.
FIR09-00708 INSP-Final Inspection5/27/20105/28/20105/28/2010 2:52:35 PMAFAIL
The north and south dry pipe systems need accellerators per NFPA 13 - 7.2.3.3 since they exceed 500 gallons. The central system does have the accellerator but did not meet the 60 second rule as per NFPA 13- 7.2.3.2 since it has 755 gallons. Also see table 7.2.3.6.1. Still need to verify low air signal to the facp for the north system and the central system. A zone map is need showing the areas covered by each sprinkler system and the location of the control valves. All signals other than the two low air signals were sent and received at the fire alarm panel.
BLD10-00502 FIRE-Final Inspection5/27/20105/28/20105/28/2010 1:28:04 PMAPASS
Life safety passed.