FIR09-00711
| INSP-Alarm Testing | 5/28/2010 | 5/28/2010 | 5/28/2010 3:32:19 PM | P | DONE |
|
|
Relocate the a/v in the dining area, provide an additional strobe in the lobby and provide an additional strobe in the courtyard corridor as discussed and then test. Still need to verify operation of the remaining smoke dampers. Need map for facp and signal report
|
BLD07-02624
| FIRE-Final Inspection | 5/27/2010 | 5/28/2010 | 5/28/2010 3:15:08 PM | A | FAIL |
|
|
Repair the two emergency lights and provide fire extinguishers with a current inspection tag.
|
BLD06-02047
| FIRE-Final Inspection | 5/27/2010 | 5/28/2010 | 5/28/2010 3:14:29 PM | A | FAIL |
|
|
Repair the two emergency lights and provide fire extinguishers with a current inspection tag.
|
FIR10-00082
| FIR-Aging Inspection | 5/28/2010 | 5/28/2010 | 5/28/2010 3:13:25 PM | | NR |
|
|
Work is in progress.
|
FIR10-00060
| INSP-Alarm Testing | 5/27/2010 | 5/28/2010 | 5/28/2010 3:12:42 PM | A | DONE |
|
|
Phase I fire alarm is complete.
|
BLD09-00557
| FIRE-Final Inspection | 5/27/2010 | 5/28/2010 | 5/28/2010 3:11:50 PM | A | FAIL |
|
|
The only item for life safety that was inspected today were the exit signs and emergency lighting. One exit sign needs to be added as shown on the city approved plans. Herb is calling in for a re-inspection for Tuesday.
|
BLD10-00608
| FIRE-Conference | 5/27/2010 | 5/28/2010 | 5/28/2010 3:07:51 PM | A | CANC |
|
|
Rescheduled for monday
|
FIR10-00026
| INSP-Final Inspection | 5/27/2010 | 5/28/2010 | 5/28/2010 3:06:22 PM | A | FAIL |
|
|
Kenny Phone #: ###-####. Everything tested ok including the fire alarm interconnect. When Kenny provides the inspection and testing form this permit can be finaled.
|
FIR09-00708
| INSP-Final Inspection | 5/27/2010 | 5/28/2010 | 5/28/2010 2:52:35 PM | A | FAIL |
|
|
The north and south dry pipe systems need accellerators per NFPA 13 - 7.2.3.3 since they exceed 500 gallons. The central system does have the accellerator but did not meet the 60 second rule as per NFPA 13- 7.2.3.2 since it has 755 gallons. Also see table 7.2.3.6.1. Still need to verify low air signal to the facp for the north system and the central system. A zone map is need showing the areas covered by each sprinkler system and the location of the control valves. All signals other than the two low air signals were sent and received at the fire alarm panel.
|
BLD10-00502
| FIRE-Final Inspection | 5/27/2010 | 5/28/2010 | 5/28/2010 1:28:04 PM | A | PASS |
|
|
Life safety passed.
|