Inspections for the day of: Tuesday, May 28, 2013.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-02921 ELE-Aging Inspection5/28/20135/28/20135/29/2013 4:03:31 PM DONE
drove by and inspected sign
ELE12-00212 ELE-Aging Inspection5/28/20135/28/20135/29/2013 10:41:50 AM DONE
Still under construction
ELE12-00491 Final5/28/20135/28/20135/28/2013 5:10:00 PMPPASS
UL listing confirmed
ELE12-01710 Electrical Rough-In5/28/20135/28/20135/28/2013 3:39:57 PMPPASS
Contact: Wes Powell Phone #: ###-#### >> Inspection requested via web by Deb Gooden South stair floors 15 thru 17 rough in ok cover
ELE13-01175 Electrical Rough-In5/28/20135/28/20135/28/2013 1:45:33 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Eric Schroeder
Overhead service conductors rough in ok
ELE13-01324 Electrical Rough-In5/28/20135/28/20135/28/2013 12:52:07 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Eric Schroeder Garage and underground conduit rough in ok cover
ELE11-02513 ELE-Aging Inspection5/28/20135/28/20135/28/2013 10:53:21 AM DONE
Drove by and finaled
ELE11-02513 Final5/28/20135/28/20135/28/2013 10:52:20 AMPPASS
Sign final ok
ELE13-01300 Temporary Service5/28/20135/28/20135/28/2013 10:43:47 AMPPASS
Temp pole Phone #: ###-#### >> Inspection requested via web by TOM BICANDI
t/s u/g n ok
ELE13-01323 Electrical Rough-In5/25/20135/28/20135/28/2013 10:24:42 AMAPASS
Job will be open after 9:00 am. The contractor will be there at 9:00. I may be there. Any questions call 870 7169. Thanks Richard Phone #: ###-#### >> Inspection requested via web by Richard Corn Upstairs bath remodel rough in ok cover
ELE13-01280 Electrical Rough-In5/23/20135/28/20135/28/2013 9:52:52 AMAPASS
Someone will be there. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan Rough in ok cover
ELE13-01326 Temporary Service5/24/20135/28/20135/28/2013 9:32:21 AMACANC
Phone #: ###-#### >> Inspection requested via web by Eric Schroeder
passed permanant service
ELE13-01326 Permanent Service5/28/20135/28/20135/28/2013 9:32:20 AMPPASS
Phone #: ###-#### >> Inspection requested via web by Eric Schroeder
p/s u/g rec ok
ELE13-01326 Permanent Service5/28/20135/28/20135/28/2013 9:31:33 AMPPASS
Phone #: ###-#### >> Inspection requested via web by Eric Schroeder
p/s u/g rec ok
ELE13-00393 Final5/27/20135/28/20135/28/2013 9:00:20 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson
-All 120 volt 15 & 20 amp recepticals shall have GFCI protection.
-Furnace disconnect shall have proper cover fit.
-Garage and outdoor recepticals not working.
-Office recepticals shall have covers and spark rings.
-Device covers needed in basement storage room.
-Basement closet fixture shall have 12" clerance to shelf.