FIR13-00213
| INSP-Final Inspection | 5/28/2013 | 5/28/2013 | 5/29/2013 5:02:02 PM | P | PASS |
|
|
Functional testing completed, inspection passed. Fire alarm permit finaled.
|
FIR13-00036
| INSP-Final Inspection | 5/28/2013 | 5/28/2013 | 5/29/2013 5:00:45 PM | P | PASS |
|
|
Fire alarm permit finaled, field adjustments approved.
|
FIR12-00108
| INSP-Sprinkler Rough-in | 5/28/2013 | 5/28/2013 | 5/28/2013 5:10:07 PM | P | PASS |
|
|
Verified noted adjustments to coverage at the 3rd to 2nd floor glass skylight, north and south stair tower 1st floor landings, EC heads at the first floor. 1st through 3rd floor work finished.
|
BLD12-03273
| FIRE-Final Inspection | 5/24/2013 | 5/28/2013 | 5/28/2013 5:04:54 PM | P | PART |
|
|
On site conference with the electrical contractor and general contractor regarding exit sign and EM lighting per IFC requirements. Discussed locations of areas to be included at the first through sixth floors, stair towers, and exit discharge.
|
BLD12-03321
| FIRE-Conference | 5/28/2013 | 5/28/2013 | 5/28/2013 4:49:12 PM | A | DONE |
|
|
Items noted during walkthrough include; building address location, missing exit discharge lighting, missing two exit signs from the kids chruch, missing EM lighting at room 123, door hardware at four breakout rooms and four meeting rooms is non-compliant, repair three EM lights, missing two exit signs at the lobby/lg. meeting room, overspaced fire extinguishers, mechanical mezzanine not shown on plans, missing small documents including the fire code review notes. Need to remove planter at the main entry/exit, post max. occupant load signage per plan annotations.
|
FIR13-00068
| INSP-Final Inspection | 5/24/2013 | 5/28/2013 | 5/28/2013 4:40:49 PM | P | NH |
|
|
No access to complete inspection due to epoxy floor finishes underway.
|
BLD13-00868
| FIRE-Final Inspection | 5/28/2013 | 5/28/2013 | 5/28/2013 4:31:10 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
FIR13-00186
| INSP-Final Inspection | 5/24/2013 | 5/28/2013 | 5/28/2013 4:30:18 PM | A | PASS |
|
|
Remainder of work completed, final walkthrough passed. Fire sprinkler permit finaled.
|