ELE14-00844
| Rough-In Permanent Service | 5/28/2014 | 5/28/2014 | 5/28/2014 12:55:14 PM | P | PASS |
|
|
Justin Phone #: ###-#### ri ok, p/s o/h rec ok
|
ELE14-01342
| Electrical Rough-In | 5/27/2014 | 5/28/2014 | 5/28/2014 11:28:22 AM | A | PASS |
|
|
jarod Phone #: ###-#### ri ok
|
ELE14-01251
| Electrical Rough-In | 5/27/2014 | 5/28/2014 | 5/28/2014 11:13:28 AM | A | PASS |
|
|
south west quarter of building rooms 134 thru 139 and hallways between the rooms Phone #: ###-#### >> Inspection requested via web by Karl Paige ri ok anop
|
ELE14-00927
| Final | 5/27/2014 | 5/28/2014 | 5/28/2014 10:44:35 AM | A | PASS |
|
|
Bud Phone #: ###-####-homeowner will only be home until noon ok final
|
ELE14-00721
| Rough-In Permanent Service | 5/27/2014 | 5/28/2014 | 5/28/2014 9:45:15 AM | A | PASS |
|
|
Call Lonny when at job trailer to get escort to duplex #2 UFER inspection. Thanks Phone #: ###-#### >> Inspection requested via web by Lonny Baum ok cover concrete encased electrode, NOTE: left correction notice for duplexes, NEC 110.26(F)(1) there shall be no foreign systems in dedicated space- no piping below panels
|
ELE14-01058
| Electrical Rough-In | 5/28/2014 | 5/28/2014 | 5/28/2014 8:36:06 AM | A | FAIL |
|
|
called to tell se cable shall not be used u/g, shall use use type, left red do not cover sticker with NEC 338.12 reference
|
ELE14-01333
| Rough-In Permanent Service | 5/23/2014 | 5/28/2014 | 5/28/2014 8:32:33 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk ri ok, p/s u/g n ok
|