Inspections for the day of: Wednesday, May 28, 2014.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00284 INSP-Sprinkler Rough-in5/28/20145/28/20145/28/2014 3:13:34 PMPPASS
Underground piping is ok to cover
FIR14-00140 INSP-Final Inspection5/27/20145/28/20145/28/2014 3:06:36 PMPFAIL
Permit not ready to final due to ceiling tile not being installed yet.
FIR14-00131 INSP-Final Inspection5/28/20145/28/20145/28/2014 2:24:50 PMPFAIL
Canceled by Brian as I pulled up. Per Brian two more pull stations are going to be added. I noted that the new pull stations currently installed too high. Also the smoke detector shown as existing located over the FACP is not installed and will unless documentation is provided showing is does not need to be installed. No actual testing was performed.
FIR14-00076 INSP-Sprinkler Rough-in5/28/20145/28/20145/28/2014 2:14:49 PMPPASS
Overhead rough-in passed for the 4" wet system from the riser room to the new "infill".
FIR13-00723 INSP-Sprinkler Rough-in5/27/20145/28/20145/28/2014 12:10:09 PMAPASS
See the city approved plans for additional locations where piping can be covered.
BLD14-00321 FIRE-Final Inspection5/27/20145/28/20145/28/2014 9:53:07 AMAPASS
Life safety passed. Panic only hardware is to be installed on door from Lobby to back offices per Carl Westfall.
BLD13-03265 FIRE-Final Inspection5/27/20145/28/20145/28/2014 9:52:01 AMAFAIL
Provide building address 4" minimum and contrasting color facing street. Remove the thumbturn lock on the main exit, keyed is ok with an indicator and sticker. Access controled egress doors to meet IFC 1008.1.9.8 (need sensor and request to exit buttons). Provide testing of the new duct smoke detectors.