Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01231 Final5/28/20195/28/20195/28/2019 4:49:19 PMPFAIL
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
No lighting changes were made.
210.71- Conference room 215 sq. ft. and larger shall have a floor receptacle installed at least 6' from a wall. 247 sq. ft. measured.
Also a conference room shall have the number of receptacles installed as if room was a residential livable room. Once number of receptacles needed has been determined they may be placed at any location owner or tenant wants. 6 minimum needed for conference room.
ELE19-01938 Electrical Rough-In5/28/20195/28/20195/28/2019 4:40:45 PMPPASS
Underground Inspection - please contact Butch w/any questions

Thank you ; have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Back patio area under ground rough in ok cover
ELE19-01656 Electrical Rough-In5/28/20195/28/20195/28/2019 4:38:32 PMPPASS
Soffit inspection Phone #: ###-#### Inspection requested via web by Ryan Wake
Soffit rough in ok cover
ELE19-01744 Electrical Rough-In5/28/20195/28/20195/28/2019 4:38:00 PMPPASS
Need a partial rough inspection so the other trades can move forward. Please call the GC (Zach Arnstam) at 2082835996 and he can explain what is ready to inspect. Phone #: ###-#### Inspection requested via web by Dan Hilke 2 required receptacles missing at rough in, 1 in nook area with in 6' of right side of door and 1 in office left side of door. Access shall be provided for fireplace fan. Contractor to fish in prior to final.
Kitchen ceiling and office addition rough in ok cover
ELE19-00482 Final5/28/20195/28/20195/28/2019 4:37:59 PMPPASS
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn
Final ok
ELE19-00933 Final5/28/20195/28/20195/28/2019 2:01:47 PMPPASS
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk
Final ok
ELE19-01059 Final5/28/20195/28/20195/28/2019 1:44:02 PMPPASS
GARAGE CODE 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn
Final ok
ELE19-01931 Final5/28/20195/28/20195/28/2019 1:10:30 PMPPASS
Final ok
ELE19-01931 Rough-In Permanent Service5/24/20195/28/20195/28/2019 1:08:43 PMPPASS
Idaho Powers connection to service weatherhead melted down, of course it wasn''t their fault but they wanted new wire in service mast. Daryl said I could replace the wire. Phone #: ###-#### Inspection requested via web by Andy Derrick
No changes to meter or mast just replaced wires in mast. p/s o/h rec ok
ELE19-01577 Rough-In Permanent Service5/24/20195/28/20195/28/2019 12:51:53 PMAPASS
Call Tony with any questions at ###-#### Phone #: ###-#### Inspection requested via web by Clayton Morgan
Basement and pool and spa to be finished in future. Rough in ok cover.
Underground to service not in at time of inspection.
p/s u/g n ok
ELE19-01872 Final5/28/20195/28/20195/28/2019 11:33:46 AMPPASS
Owners 85 year old mother contacted a friend Ken Travis which contacted me to see if we could meet and take care of inspections. Agreed only due to age of mother and her frustration with dealing with issue. In future a discription of work must be included in notes or job will fail and re-inspection fees will be assessed. Final ok
ELE19-01872 Electrical Rough-In5/28/20195/28/20195/28/2019 11:29:07 AMPPASS
Changed furnace and added AC unit at rear of house. Rough in ok
ELE19-01933 Rough-In Permanent Service5/27/20195/28/20195/28/2019 11:17:26 AMAPASS
Wire house and garage Phone #: ###-#### Inspection requested via web by John VanZandt Rough in ok cover p/s o/h n ok
ELE19-01483 Final5/27/20195/28/20195/28/2019 10:34:03 AMAPASS
Please call ahead Phone #: ###-#### Inspection requested via web by Kyle Dillon
Final ok
ELE19-00601 Electrical Rough-In5/23/20195/28/20195/28/2019 10:07:47 AMAPASS
UG cover. Danny is the contact. Thanks Phone #: ###-#### Inspection requested via web by Buster Bowen
Underslab western 1/3rd as noted on contractor print rough in ok cover.
ELE19-01825 Temporary Service5/24/20195/28/20195/28/2019 9:25:10 AMAPASS
Jake is the contact Phone #: ###-#### Inspection requested via web by Deb Ipsen
Temp service energized prior to inspection. t/s o/h n ok
ELE18-03983 Final5/21/20195/28/20195/28/2019 8:47:01 AMANR
Phone #: ###-#### Inspection requested via web by Barbara Szurgot
Unable to test GFCI due to service change being done same day. Recall when ready.
ELE19-01713 Permanent Service5/21/20195/28/20195/28/2019 8:37:25 AMAPASS
We would like to request inspector to be there by 8:00 am. Idaho Power coming to turn power back on to business at 8. Phone #: ###-#### Inspection requested via web by Barbara Szurgot
Compressor and 1 sub panel fed with 2/0, need fuse down or increase wire size. Strapping needed thru out. Not sure if GFCI protection has ever been checked for automotive repair.
p/s u/g rec ok