ELE03-01146
| Electrical Rough-In | 5/28/2003 | 5/29/2003 | 5/29/2003 12:00:00 AM | A | FAIL |
|
|
Wall rough-in.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs
cor.posted called 300.4(A)(1)&(D), 250.148 grd outside boxes 5/29/2003 9:53:03 AM
|
ELE02-03173
| Permanent Service | 5/28/2003 | 5/29/2003 | 5/29/2003 12:00:00 AM | A | PASS |
|
|
CONTACT GREG OYAMA SERVICE INSPECTION ONLY; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
p/s u/g new ok for duplex 5/29/2003 9:06:40 AM
|
ELE03-01570
| Final | 5/29/2003 | 5/29/2003 | 5/29/2003 12:00:00 AM | P | FAIL |
|
|
###-#### ingrid cor. posted called 250.142(B) needs 4 wire for range and dryer from sub panel, need outlet for a/c, bond hot and cold see added p/s 5/29/2003 2:48:11 PM
|
ELE03-01572
| Final | 5/29/2003 | 5/29/2003 | 5/29/2003 12:00:00 AM | P | PASS |
|
|
PAT; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 5/29/2003 2:00:21 PM
|
ELE03-01397
| Final | 5/29/2003 | 5/29/2003 | 5/29/2003 12:00:00 AM | P | PASS |
|
|
PAT; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 5/29/2003 4:15:58 PM
|
ELE03-01568
| Final | 5/29/2003 | 5/29/2003 | 5/29/2003 12:00:00 AM | P | PASS |
|
|
shawn; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok survey posted 250.122 grd dryer with #10 250.52(A) grd within 5 ft, 230.24(B) 10 ft clearence from drip loop to grade called 5/29/2003 3:38:25 PM
|
ELE01-03617
| Electrical Rough-In | 5/29/2003 | 5/29/2003 | 5/29/2003 12:00:00 AM | P | PART |
|
|
walls 2nd floor office ok 5/29/2003 12:41:09 PM
|
ELE03-01572
| Electrical Rough-In | 5/29/2003 | 5/29/2003 | 5/29/2003 12:00:00 AM | P | PASS |
|
|
r/i for a/c
|
ELE03-01570
| Permanent Service | 5/29/2003 | 5/29/2003 | 5/29/2003 12:00:00 AM | P | CANC |
|
|
p/s o/h rec. ok
|
ELE03-01568
| Permanent Service | 5/29/2003 | 5/29/2003 | 5/29/2003 12:00:00 AM | P | PASS |
|
|
p/s o/h rec. ok
|