Inspections for the day of: Thursday, May 29, 2008.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-00041 Final5/29/20085/29/20085/29/2008 2:51:02 PMPPASS
trevin Phone #: ###-#### - please call 1/2 hr prior to inspection ok , no ESC permit
ELE08-01419 Electrical Rough-In5/29/20085/29/20085/29/2008 2:29:09 PMPPART
wayne-- r/i under slab Phone #: ###-#### ok no ESC permit
ELE08-01352 Permanent Service5/28/20085/29/20085/29/2008 1:26:32 PMPFAIL
ok for idaho power to connect Phone #: ###-#### Internet Inspection Request from: Randy Fletcher corr called needs 50 amp max breaker for trailer, shall not bury the cord, shall not ID 6 or smaller neutral shall be white, make sure #10 equip grd , no ESC permit
ESC08-00172 General Inspection5/29/20085/29/20085/29/2008 12:35:33 PMPPASS
site clean no violations
ELE08-00883 Final5/29/20085/29/20085/29/2008 12:34:33 PMPPASS
bill Phone #: ###-#### ok called shall not ID #10 black as geen equip grd, reversed polarity back outside gfci survey
ESC08-00140 Random Inspection5/29/20085/29/20085/29/2008 10:39:22 AMAPART
site is clean, dirt piles stable
ELE08-00801 Electrical Rough-In5/28/20085/29/20085/29/2008 10:36:30 AMAPART
tenant improvement inspection please. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS
walls hard ceilings ok needs to protect #1 alum at 100 amps, and terminate water bond at neutral bus
ELE08-00800 Rough-In Permanent Service5/28/20085/29/20085/29/2008 10:35:04 AMAPASS
rough-in permanant service on shell. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS
r/i p/s u/g new ok
ESC08-00244 Random Inspection5/29/20085/29/20085/29/2008 9:53:11 AMAPART
site ok
ELE08-01126 Final5/29/20085/29/20085/29/2008 9:52:12 AMAPASS
Scheduled by a contractor via Hello! on 5/29/2008 at 5:44:35 AM. Contact: ###-####. ok
ELE08-01395 Final5/28/20085/29/20085/29/2008 9:05:43 AMAPASS
Jessie; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
ok
ESC08-00385 Random Inspection5/29/20085/29/20085/29/2008 8:27:21 AMAPART
site clean and card posted
ELE08-01277 Electrical Rough-In5/28/20085/29/20085/29/2008 8:26:16 AMAPART
this is a swimming pool. the inspection need is for the potting and equipotential grid. Thanks! Phone #: ###-#### Internet Inspection Request from: Chris Weimar
ok no e grid required