ELE04-00041
| Final | 5/29/2008 | 5/29/2008 | 5/29/2008 2:51:02 PM | P | PASS |
|
|
trevin Phone #: ###-#### - please call 1/2 hr prior to inspection ok , no ESC permit
|
ELE08-01419
| Electrical Rough-In | 5/29/2008 | 5/29/2008 | 5/29/2008 2:29:09 PM | P | PART |
|
|
wayne-- r/i under slab Phone #: ###-#### ok no ESC permit
|
ELE08-01352
| Permanent Service | 5/28/2008 | 5/29/2008 | 5/29/2008 1:26:32 PM | P | FAIL |
|
|
ok for idaho power to connect Phone #: ###-#### Internet Inspection Request from: Randy Fletcher corr called needs 50 amp max breaker for trailer, shall not bury the cord, shall not ID 6 or smaller neutral shall be white, make sure #10 equip grd , no ESC permit
|
ESC08-00172
| General Inspection | 5/29/2008 | 5/29/2008 | 5/29/2008 12:35:33 PM | P | PASS |
|
|
site clean no violations
|
ELE08-00883
| Final | 5/29/2008 | 5/29/2008 | 5/29/2008 12:34:33 PM | P | PASS |
|
|
bill Phone #: ###-#### ok called shall not ID #10 black as geen equip grd, reversed polarity back outside gfci survey
|
ESC08-00140
| Random Inspection | 5/29/2008 | 5/29/2008 | 5/29/2008 10:39:22 AM | A | PART |
|
|
site is clean, dirt piles stable
|
ELE08-00801
| Electrical Rough-In | 5/28/2008 | 5/29/2008 | 5/29/2008 10:36:30 AM | A | PART |
|
|
tenant improvement inspection please. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS walls hard ceilings ok needs to protect #1 alum at 100 amps, and terminate water bond at neutral bus
|
ELE08-00800
| Rough-In Permanent Service | 5/28/2008 | 5/29/2008 | 5/29/2008 10:35:04 AM | A | PASS |
|
|
rough-in permanant service on shell. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS r/i p/s u/g new ok
|
ESC08-00244
| Random Inspection | 5/29/2008 | 5/29/2008 | 5/29/2008 9:53:11 AM | A | PART |
|
|
site ok
|
ELE08-01126
| Final | 5/29/2008 | 5/29/2008 | 5/29/2008 9:52:12 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/29/2008 at 5:44:35 AM. Contact: ###-####. ok
|
ELE08-01395
| Final | 5/28/2008 | 5/29/2008 | 5/29/2008 9:05:43 AM | A | PASS |
|
|
Jessie; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok
|
ESC08-00385
| Random Inspection | 5/29/2008 | 5/29/2008 | 5/29/2008 8:27:21 AM | A | PART |
|
|
site clean and card posted
|
ELE08-01277
| Electrical Rough-In | 5/28/2008 | 5/29/2008 | 5/29/2008 8:26:16 AM | A | PART |
|
|
this is a swimming pool. the inspection need is for the potting and equipotential grid. Thanks! Phone #: ###-#### Internet Inspection Request from: Chris Weimar ok no e grid required
|