FIR07-00812
| INSP-Sprinkler Rough-in/Hydro | 5/28/2008 | 5/29/2008 | 5/30/2008 11:43:20 AM | A | FAIL |
|
|
Inspection for the office areas only second and first floors north side completed today, noted SW head at the first floor stair landing is too low, line under the staris at the warehouse is 1 1/4 fed by a 1" tap-also missing ret. strap at a beam clamp, will require as-built plans for the second floor branchline pipe size changes, stairway heads at the 2nd floor are not complete, verified items from previous inspection are done, okayed for cover at the drop ceilings.
|
FIR08-00180
| INSP-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 6:07:18 PM | A | NR |
|
|
Scheduled by a contractor via Hello! on 5/28/2008 at 3:15:38 PM. Contact: ###-####.
|
BLD07-02932
| FIRE-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 6:04:01 PM | A | FAIL |
|
|
Project related fire sprinkler permits are not ready for final, noted new beer cooler does not provide adequate egress under door failure conditions.
|
FIR08-00124
| INSP-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 6:02:01 PM | A | FAIL |
|
|
Defficiencies noted include missing stock of ESFR heads at the riser head box, overspaced upright heads at the new grade level riser room, 3 branchlines at the warehouse area are too low for pendent ESFR head listing, pendent heads at the office storage room and men's restroom are obstructed by surface mounted lights, DP at the cooler condensers have been added.
|
FIR08-00067
| INSP-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 3:49:39 PM | A | FAIL |
|
|
Correction items are not complete, still require alarm line shutoff valve supervision at all six risers.
|
FIR07-00830
| INSP-Alarm Testing | 5/28/2008 | 5/29/2008 | 5/29/2008 1:44:49 PM | A | PART |
|
|
See approved plans for areas inspected today. Noted smoke detectors at six patient rooms were relocated and tested as per Forrest notes, construction is still underway at some locations.
|
BLD08-00632
| FIRE-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 1:43:14 PM | A | DONE |
|
|
Permit details indicate no fire inspection related signatures are required for this project, work scheduled for a structural final.
|
BLD08-00752
| FIRE-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 1:40:03 PM | A | PASS |
|
|
Fire life safety inspection passed, okayed temp suite address signage until permanent is delivered.
|
FIR08-00294
| INSP-Sprinkler Rough-in | 5/28/2008 | 5/29/2008 | 5/29/2008 1:27:12 PM | A | CANC |
|
|
john Phone #: ###-#### NOTE: Inspection type does not correlate with permit description for work performed.
|
BLD08-00897
| FIRE-Final Inspection | 5/27/2008 | 5/29/2008 | 5/29/2008 1:16:40 PM | A | DEFR |
|
|
2 of 2 scheduled in this time slot...other is FA / Horn & Strobe Final Phone #: ###-#### Internet Inspection Request from: Wayne Berry
|
FIR08-00333
| INSP-Final Inspection | 5/27/2008 | 5/29/2008 | 5/29/2008 1:16:21 PM | A | DEFR |
|
|
1 of 2 scheduled in this time slot. Life safety on BLD will be the 2nd. Phone #: ###-#### Internet Inspection Request from: Wayne Berry
|
FIR07-00606
| INSP-Sprinkler Rough-in/Hydro | 5/28/2008 | 5/29/2008 | 5/29/2008 1:16:04 PM | A | PART |
|
|
See previous inspection notes for activities to date.
|
FIR08-00168
| INSP-Alarm Testing | 5/28/2008 | 5/29/2008 | 5/29/2008 12:58:36 PM | P | PART |
|
|
Listed correction notice items verified for compliance, permit final pending completion of phase two remodel work at the east side including notification appliances and riser #2 alarm and supervisory conditions.
|
BLD08-00725
| FIRE-Final Inspection | 5/29/2008 | 5/29/2008 | 5/29/2008 12:54:47 PM | P | FAIL |
|
|
Remove manual thumbturn at the main entry/exit door, post missing suite address numbers, PFE needs to be posted as discussed.
|
FIR07-00946
| INSP-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 11:25:45 AM | A | PASS |
|
|
Test all new devices add for elevator recall per state inspection. KR
|
FIR08-00349
| INSP-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 9:44:03 AM | A | PASS |
|
|
Sprinkler inspection completed.KR
|
FIR08-00018
| FIR-Aging Inspection | 5/29/2008 | 5/29/2008 | 5/29/2008 7:51:28 AM | | DONE |
|
|
Work in progress, construction underway.
|