FIR08-00237
| INSP-Final Inspection | 5/29/2008 | 5/29/2008 | 5/29/2008 4:52:00 PM | P | FAIL |
|
|
The north duct smoke detector in the Billiards store did not shut down the hvac unit as per chapter 6 of the IMC. The other duct smoke detectors operated correctly.
|
FIR07-00886
| INSP-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 4:50:27 PM | P | CANC |
|
|
Jeremiah, please call 30 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|
FIR08-00221
| INSP-Sprinkler Rough-in | 5/28/2008 | 5/29/2008 | 5/29/2008 3:23:30 PM | A | PASS |
|
|
The underground piping can be buried and it has also been flushed.
|
FIR08-00204
| INSP-Supply line flush | 5/28/2008 | 5/29/2008 | 5/29/2008 3:14:03 PM | A | PASS |
|
|
Underground flush passed.
|
BLD08-00169
| FIRE-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 2:03:12 PM | P | PASS |
|
|
Fire life safety completed. KR
|
FIR08-00098
| INSP-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 2:02:26 PM | P | PASS |
|
|
Fire alarm tasting completed.KR
|
FIR07-00949
| INSP-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 2:01:25 PM | P | PASS |
|
|
Fire sprinklers for shell completed.KR
|
BLD07-02677
| FIRE-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 2:00:14 PM | P | PASS |
|
|
Fire life safety completed. KR
|
BLD08-00169
| FIRE-Alarm Testing | 5/28/2008 | 5/29/2008 | 5/29/2008 1:55:08 PM | P | PASS |
|
|
Fire life safety completed. See fir08-00098 for alarm testing. KR
|
FIR08-00201
| INSP-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 1:53:16 PM | P | PASS |
|
|
Fire alarm testing completed.KR
|
BLD07-02677
| FIRE-Alarm Testing | 5/28/2008 | 5/29/2008 | 5/29/2008 1:51:50 PM | P | PASS |
|
|
Fire life safety completed. See fir08-00201 for fire alarm testing. KR
|
BLD08-00552
| FIRE-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 1:05:40 PM | A | PASS |
|
|
Life safety passed
|
BLD08-00675
| FIRE-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 11:57:59 AM | A | PASS |
|
|
Fire life safety passed
|
BLD08-00546
| FIRE-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 10:13:27 AM | A | PASS |
|
|
Life safety passed.
|
FIR08-00263
| INSP-Final Inspection | 5/23/2008 | 5/29/2008 | 5/29/2008 9:55:50 AM | A | PASS |
|
|
Permit finaled
|
FIR07-00874
| INSP-Sprinkler Rough-in/Hydro | 5/28/2008 | 5/29/2008 | 5/29/2008 8:55:34 AM | A | DONE |
|
|
The 24 hour air test was begun with 42psi on both the ALF and the Nurses Station dry systems at 8:15am. It also appears that many of the pendant heads do not meet the three times rule from the light fixtures.
|
FIR08-00232
| INSP-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 8:42:24 AM | A | PASS |
|
|
Permit finaled
|
FIR08-00233
| INSP-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 7:49:24 AM | A | PASS |
|
|
Permit finaled
|