Inspections for the day of: Thursday, May 29, 2008.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00237 INSP-Final Inspection5/29/20085/29/20085/29/2008 4:52:00 PMPFAIL
The north duct smoke detector in the Billiards store did not shut down the hvac unit as per chapter 6 of the IMC. The other duct smoke detectors operated correctly.
FIR07-00886 INSP-Final Inspection5/28/20085/29/20085/29/2008 4:50:27 PMPCANC
Jeremiah, please call 30 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
FIR08-00221 INSP-Sprinkler Rough-in5/28/20085/29/20085/29/2008 3:23:30 PMAPASS
The underground piping can be buried and it has also been flushed.
FIR08-00204 INSP-Supply line flush5/28/20085/29/20085/29/2008 3:14:03 PMAPASS
Underground flush passed.
BLD08-00169 FIRE-Final Inspection5/28/20085/29/20085/29/2008 2:03:12 PMPPASS
Fire life safety completed. KR
FIR08-00098 INSP-Final Inspection5/28/20085/29/20085/29/2008 2:02:26 PMPPASS
Fire alarm tasting completed.KR
FIR07-00949 INSP-Final Inspection5/28/20085/29/20085/29/2008 2:01:25 PMPPASS
Fire sprinklers for shell completed.KR
BLD07-02677 FIRE-Final Inspection5/28/20085/29/20085/29/2008 2:00:14 PMPPASS
Fire life safety completed. KR
BLD08-00169 FIRE-Alarm Testing5/28/20085/29/20085/29/2008 1:55:08 PMPPASS
Fire life safety completed. See fir08-00098 for alarm testing. KR
FIR08-00201 INSP-Final Inspection5/28/20085/29/20085/29/2008 1:53:16 PMPPASS
Fire alarm testing completed.KR
BLD07-02677 FIRE-Alarm Testing5/28/20085/29/20085/29/2008 1:51:50 PMPPASS
Fire life safety completed. See fir08-00201 for fire alarm testing. KR
BLD08-00552 FIRE-Final Inspection5/28/20085/29/20085/29/2008 1:05:40 PMAPASS
Life safety passed
BLD08-00675 FIRE-Final Inspection5/28/20085/29/20085/29/2008 11:57:59 AMAPASS
Fire life safety passed
BLD08-00546 FIRE-Final Inspection5/28/20085/29/20085/29/2008 10:13:27 AMAPASS
Life safety passed.
FIR08-00263 INSP-Final Inspection5/23/20085/29/20085/29/2008 9:55:50 AMAPASS
Permit finaled
FIR07-00874 INSP-Sprinkler Rough-in/Hydro5/28/20085/29/20085/29/2008 8:55:34 AMADONE
The 24 hour air test was begun with 42psi on both the ALF and the Nurses Station dry systems at 8:15am. It also appears that many of the pendant heads do not meet the three times rule from the light fixtures.
FIR08-00232 INSP-Final Inspection5/28/20085/29/20085/29/2008 8:42:24 AMAPASS
Permit finaled
FIR08-00233 INSP-Final Inspection5/28/20085/29/20085/29/2008 7:49:24 AMAPASS
Permit finaled