FIR08-00786
| INSP-Alarm Testing | 5/26/2009 | 5/29/2009 | 5/29/2009 4:58:04 PM | A | PART |
|
|
Completed fire alarm testing for the second floor classroom wings areas F and G. Noted three smoke detectors to be moved due to overspacing, one notification appliance is overspaced, also annotated field changes including deleted dampers, door holds and smoke detectors at some areas.
|
BLD09-00528
| FIRE-Final Inspection | 5/28/2009 | 5/29/2009 | 5/29/2009 2:00:23 PM | A | PASS |
|
|
Fire life safety for the portion of demo permit work indicated passed inspection for both upper and lower floor levels.
|
BLD08-02331
| FIRE-Final Inspection | 5/28/2009 | 5/29/2009 | 5/29/2009 1:56:29 PM | A | PASS |
|
|
C/N items are complete, fire life safety inspection passed. NOTE: No inspection card available on site for signature.
|
BLD08-01796
| FIRE-Final Inspection | 5/29/2009 | 5/29/2009 | 5/29/2009 1:55:33 PM | P | PASS |
|
|
Shell building fire life safety inspection completed satisfactory.
|
BLD08-01797
| FIRE-Final Inspection | 5/28/2009 | 5/29/2009 | 5/29/2009 1:52:58 PM | A | PASS |
|
|
Fire life safety final inspection passed, one missing fire extinguisher at the mezzanine level provided while on site, temp building address numbers posted per request, project related FIR permits are finaled.
|
FIR09-00133
| INSP-Final Inspection | 5/28/2009 | 5/29/2009 | 5/29/2009 1:50:16 PM | A | PASS |
|
|
Verified a listed air maintenance device has been installed, fire sprinkler permit approved for final.
|
BLD09-00781
| FIRE-Final Inspection | 5/28/2009 | 5/29/2009 | 5/29/2009 1:49:01 PM | A | PASS |
|
|
Noted two items to be completed prior to structural final including post the max. occupant load sign per review notes at 66 and provide approved door hardware at the mens restroom per discussion. Also noted building is not fire sprinklered as indicated on review. Remainder of life safety items okayed.
|
FIR09-00106
| INSP-Final Inspection | 5/28/2009 | 5/29/2009 | 5/29/2009 1:43:41 PM | A | PASS |
|
|
Verified plan resubmittals, noted corrections are finished, fire sprinkler permit finaled.
|