Inspections for the day of: Wednesday, May 29, 2013.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00216 INSP-Sprinkler Rough-in5/29/20135/29/20135/30/2013 12:30:10 PMPPART
Overhead fire sprinkler work above the grid ceilings okayed for cover.
FIR13-00101 INSP-Sprinkler Rough-in5/29/20135/29/20135/29/2013 4:58:30 PMPPART
Point of connection to building riser stub okayed for bury- flushing to be completed prior to final.
BLD13-00807 FIRE-Conference5/29/20135/29/20135/29/2013 12:37:04 PMPDONE
Discussion with contractor regarding fire extinguisher placement, project related trade work and finish schedule.
BLD13-01264 FIRE-Final Inspection5/29/20135/29/20135/29/2013 12:24:41 PMAPART
Final pending remainder of noted correction items including hardware and main entry/exit signage.
FIR13-00116 INSP-Sprinkler Rough-in5/29/20135/29/20135/29/2013 12:19:05 PMAPART
UG including the tie-in and 45 ell okay for cover. Overhead work in progress.
BLD13-00868 FIRE-Final Inspection5/29/20135/29/20135/29/2013 12:14:50 PMAPASS
Phase one and two completed, inspection passed.
BLD11-00407 FIRE-Final Inspection5/29/20135/29/20135/29/2013 12:13:17 PMAPASS
Life safety inspection completed and passed.