Inspections for the day of: Thursday, May 29, 2014.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-00342 FIRE-Conference5/29/20145/29/20145/29/2014 4:46:50 PMPDONE
Discussion with contractor regarding fire sprinkler work, existing cooking hood, scope of remodel, etc.
BLD14-00370 FIRE-Final Inspection5/28/20145/29/20145/29/2014 4:39:27 PMPPASS
Fire life safety inspection completed acceptable.
FIR14-00251 INSP-Final Inspection5/29/20145/29/20145/29/2014 4:38:31 PMPPASS
Fire sprinkler permit approved for final once escutcheons are installed.
BLD14-01049 FIRE-Conference5/29/20145/29/20145/29/2014 4:36:15 PMPDONE
On site conference regarding exit sign locations.
BLD14-01077 FIRE-Final Inspection5/28/20145/29/20145/29/2014 2:06:50 PMAPASS
Life safety final approved.
FIR14-00239 INSP-Sprinkler Rough-in5/28/20145/29/20145/29/2014 1:32:05 PMAPART
Overhead fire sprinkler modifications at the remodel area passed rough-in. Need to re-insulate for cold cavity protection as discussed prior to final.
FIR13-00608 INSP-Sprinkler Rough-in5/28/20145/29/20145/29/2014 11:40:10 AMAPART
Field modifications at the 5th floor "staging 612" room passed rough-in, and are approved for cover pending changes included on record drawings.
FIR14-00241 INSP-Sprinkler Rough-in5/28/20145/29/20145/29/2014 10:52:41 AMAPART
Plaza grille area tie-ins and head changes at the south end passed inspection. Rough-in okayed.
FIR13-00440 INSP-Sprinkler Rough-in5/28/20145/29/20145/29/2014 10:49:20 AMAPART
Basement level elevator lobby grid ceiling as marked and dated on approved plans okayed for cover.
BLD14-01048 FIRE-Conference5/28/20145/29/20145/29/2014 10:48:05 AMADONE
On site conference regarding new and existing exit sign locations.