Inspections for the day of: Friday, May 29, 2020.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-01828 Rough-In Permanent Service5/29/20205/29/20205/29/2020 1:47:12 PMPFAIL
Inspection requested via web by Hidajet Zahic 210.52(I)- Foyers 60 sq ft. and larger shall have a receptacle oultet installed on all wall 3' and wider.
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface nail plates shall be installed to protect cables from physical damage. Corners drilled at 45 degree angles.
334.23- All NM cables in attic run within 7' of attic access shall be protected from damage by installed guard strips. Guard strips installed but NM cables run on top on guard strip.
334.30- NM cables shall have supports not to exceed 4 1/2'. 14-3 runs entire lengthh of kitchen with 0 support points.
ELE17-04283 Final5/28/20205/29/20205/29/2020 11:31:18 AMAPASS
Call me 1/2 hour before and i will meet you there please. Chris 208 871 9431 Phone #: ###-#### Inspection requested via web by Chris Husted Final ok
ELE20-00996 Final5/28/20205/29/20205/29/2020 10:50:39 AMAPASS
Garage code 1979E Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE20-01481 Final5/29/20205/29/20205/29/2020 10:22:03 AMPPASS
Shed power not this contractors scope of work, installed rough in of underground conduit to shed only. Final ok
ELE20-00507 Final5/29/20205/29/20205/29/2020 10:12:40 AMAPASS
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard Final ok
ELE20-01481 Final5/28/20205/29/20205/29/2020 9:38:15 AMAFAIL
screened - Mike Phone #: ###-#### 225.31- Disconnecting Means. Means shall be provided for disconnecting all ungrounded conductors that supply or pass through the building or structure.
Shed is existing and interior wiring it is refed by new mobile home.
ELE20-01794 Electrical Rough-In5/28/20205/29/20205/29/2020 9:03:55 AMAPASS
Underground inspection- City approved plans are on site now. Phone #: ###-#### Inspection requested via web by Shane Lott
General contractor asked about 1 siding walls, informed not to cover in any way prior to a rough in inspection as per BCC 4-05-23.
Underslab rough in ok cover.