ELE20-01828
| Rough-In Permanent Service | 5/29/2020 | 5/29/2020 | 5/29/2020 1:47:12 PM | P | FAIL |
|
|
Inspection requested via web by Hidajet Zahic 210.52(I)- Foyers 60 sq ft. and larger shall have a receptacle oultet installed on all wall 3' and wider. 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface nail plates shall be installed to protect cables from physical damage. Corners drilled at 45 degree angles. 334.23- All NM cables in attic run within 7' of attic access shall be protected from damage by installed guard strips. Guard strips installed but NM cables run on top on guard strip. 334.30- NM cables shall have supports not to exceed 4 1/2'. 14-3 runs entire lengthh of kitchen with 0 support points.
|
ELE17-04283
| Final | 5/28/2020 | 5/29/2020 | 5/29/2020 11:31:18 AM | A | PASS |
|
|
Call me 1/2 hour before and i will meet you there please. Chris 208 871 9431 Phone #: ###-#### Inspection requested via web by Chris Husted Final ok
|
ELE20-00996
| Final | 5/28/2020 | 5/29/2020 | 5/29/2020 10:50:39 AM | A | PASS |
|
|
Garage code 1979E Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
|
ELE20-01481
| Final | 5/29/2020 | 5/29/2020 | 5/29/2020 10:22:03 AM | P | PASS |
|
|
Shed power not this contractors scope of work, installed rough in of underground conduit to shed only. Final ok
|
ELE20-00507
| Final | 5/29/2020 | 5/29/2020 | 5/29/2020 10:12:40 AM | A | PASS |
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard Final ok
|
ELE20-01481
| Final | 5/28/2020 | 5/29/2020 | 5/29/2020 9:38:15 AM | A | FAIL |
|
|
screened - Mike Phone #: ###-#### 225.31- Disconnecting Means. Means shall be provided for disconnecting all ungrounded conductors that supply or pass through the building or structure. Shed is existing and interior wiring it is refed by new mobile home.
|
ELE20-01794
| Electrical Rough-In | 5/28/2020 | 5/29/2020 | 5/29/2020 9:03:55 AM | A | PASS |
|
|
Underground inspection- City approved plans are on site now. Phone #: ###-#### Inspection requested via web by Shane Lott General contractor asked about 1 siding walls, informed not to cover in any way prior to a rough in inspection as per BCC 4-05-23. Underslab rough in ok cover.
|