Inspections for the day of: Tuesday, May 3, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01355 Electrical Rough-In5/2/20055/3/20055/3/2005 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 5/2/2005 at 12:18:30 PM. Contact: ###-####. cor. posted met owner spray booth shall be listed or field evaluated, loose set screws, replace damaged wire air compressor, use manufactures listed breakers only 5/3/2005 10:48:55 AM
ELE05-00922 Final5/2/20055/3/20055/3/2005 12:00:00 AMAPASS
jeff; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok card signed 5/3/2005 12:10:48 PM
ELE05-00316 Final5/2/20055/3/20055/3/2005 12:00:00 AMAFAIL
arron--call 1st for access; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie cor. posted called needs out wall space dinning area 210.52(A&B) 5/3/2005 8:37:15 AM
ELE04-00795 Electrical Rough-In5/2/20055/3/20055/3/2005 12:00:00 AMANH
Scheduled by a contractor via Hello! on 5/2/2005 at 3:16:26 PM. Contact: ###-####. called notice posted 5/3/2005 10:49:38 AM
ELE05-00387 Conference5/3/20055/3/20055/3/2005 12:00:00 AMADONE
call prior to arrival so i can meet you there; Phone #: ###-#### Internet Inspection Request from: joe wheeler ok 5/3/2005 9:29:20 AM
ELE05-01455 Final5/3/20055/3/20055/3/2005 12:00:00 AMAPASS
As early as possible.; Phone #: ###-#### Internet Inspection Request from: Richard Jones ok 5/3/2005 8:14:00 AM
ELE05-00345 Final5/3/20055/3/20055/3/2005 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 5/3/2005 at 8:01:57 AM. Contact: ###-####. cor. posted met contractor 250.8 no SMS for grds or bonds, 250.148 grd metal boxes, needs UL listed RT fittings, 210.5A B C 314. 29 access to box, 300.10&12 314.14 needs access to boxes with fixtures mounted over them 5/3/2005 3:11:05 PM
ELE05-01524 Rough-In Permanent Service5/3/20055/3/20055/3/2005 12:00:00 AMPPASS
bob ###-#### r/i ok p/s o/h new ok 5/3/2005 1:14:02 PM
ELE05-01529 Electrical Rough-In5/3/20055/3/20055/3/2005 12:00:00 AMPPART
under slab inspection ###-#### dill ok 5/3/2005 3:27:05 PM
ELE05-01535 Temporary Service5/3/20055/3/20055/3/2005 12:00:00 AMPPASS
mike ###-#### t/s u/h new ok 5/3/2005 3:26:55 PM
ELE05-01532 Electrical Rough-In5/3/20055/3/20055/3/2005 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 5/3/2005 at 11:21:46 AM. Contact: ###-####. outside soffits 5/3/2005 2:17:37 PM